Herunterladen Inhalt Inhalt Diese Seite drucken

Electric Wiring Work - mundoclima MUSTR-H8 Installationshandbuch

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 105
INSTALLATION MANUAL
5.

ELECTRIC WIRING WORK

General instructions
All field wiring and components must be installed by a licensed
electrician and must comply with relevant European and national
regulations.
Use copper wire only.
Follow the 'Wiring diagram' attached to the unit body to wire the
outdoor unit, indoor units and the remote controller.
A circuit breaker capable of shutting down power supply to the
entire system must be installed.
Note that the operation will restart automatically if the main
power supply is turned off and then turned back on again.
Be sure to ground the air conditioner.
Do not connect the ground wire to gas pipes, water pipes,
lightning rods, or telephone ground wires.
-
Gas pipes: might cause explosions or fire if gas leaks.
-
Water pipes: no grounding effect if hard vinyl piping is used
-
T
elephone ground wires or lightning rods: might cause
abnormally highelectric potential in the ground during
lightning storms
.
The specification of power
Model
Phase
Frequency and
Voltage
INDOOR
POWER
UNIT
WIRING (mm
POWER
CIRCUIT
BREAKER/
Fuse (A)
Phase
Frequency and
Voltage
OUTDOOR
POWER
UNIT
WIRING (mm
POWER
CIRCUIT
BREAKER/
Fuse (A)
Indoor/Outdoor Connecting
2
Wiring (mm
)
Wiring diagrams for power and interconnection between the outdoor unit and the indoor unit:
MUSTR-18-H8
INDOOR UNIT
S2 S1
L(L1) N(L2)
230 Vac
50 Hz
Use shielded cable for interconnection
Note: Interconnection terminal S1 can be called P, and S2 as Q.
MUSTR-18/24-H8
MUSTR-30/36-H8
1-phase
220-240V, 50Hz
220-240V, 50Hz
3×1.0
2
)
15/10
1-phase
220-240V, 50Hz
220-240V, 50Hz
3×2.5
2
)
30/20
2×0.75 (Shielded)
2×0.75 (Shielded)
OUTDOOR UNIT
No use
Minimum norminal cross-sectional
area of conductors:
Rated current
of appliance
(A)
<6
>6 and <10
>10 and <16
>16 and <25
>25 and <32
>32 and <45
>45 and <60
NOTE:
The cable size and the current of the fuse or switch are determined by the
maximum current indicated on the nameplate which located on the side panel
of the unit. Please refer to the nameplate before selecting the cable, fuse and
switch.
.
MUSTR-48-H8
1-phase
1-phase
220-240V, 50Hz
3×1.0
3×1.0
15/10
15/10
1-phase
1-phase
220-240V, 50Hz
3×6.0
3×4.0
40/30
40/35
2×0.75 (Shielded)
230 Vac
50 Hz
49
Nominal cross-sectional
area
(mm2)
0.75
1.0
1.5
2.5
4.0
6.0
10.0
MUSTR-48/60-H8T
1-phase
220-240V, 50Hz
3×1.0
15/10
3-phase
380-420V, 50Hz
5×2.5
30/25
2×0.75 (Shielded)

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis