Technical Data - OBO Bettermann V20-...-280 serie Installationsanleitung

Surge controller
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 6
Installation instructions
• Clamp the protection device onto the hat rail,
ensuring that the lockable hat rail holder is un-
locked (Figure
).
2
• Maintain the stripping length and tightening
torque (Figure
).
• Connection according to the circuit diagram
(TN systems or TN-S / TT systems).
Dismantling
Figure
:
• Unlock and remove arresters in the manner
shown.
• Open the hat rail holder with a flat screwdriver
and engage it (see also Figure
the protection devices.
Faults
If the integrated cut-off unit trips (e.g. due to age
on account of multiple, very high overvoltages),
the visual display (Figure
(grey) to red. In this case, remove the arrester
and insert a new arrester (available separately,
V20: item no. 5095 364, C20: item no. 5095 600).
In the case of devices with multiple arresters, it
must be assumed that the other arresters of this
device have experienced the same load. We rec-
ommend that you check them and, if necessary,
also replace them. Dispose of replaced arrest-
ers.
Remote signalling
Figure
(only V20-..+FS..):
When at least one arrester is disconnected, the
changeover contact in the remote signalling mod-
ule switches from 11/12 to 11/14. Remote signal-
ling can be switched as an NO or NC contact.
This allows control of suitable signalling compo-
nents (e.g. central error messages, light or
acoustic signal).
• Connect the remote signalling cables as
shown, in so doing maintaining the specified
cable cross-section and the stripping length.
Maintenance
We recommend carrying out a visual check of
the visual display every 2-4 years or after light-
ning strikes.
OBO Bettermann GmbH & Co. KG
). Remove
2
) switches from green
Disposal
– Packaging as household waste
– Protection device/arrester as electronic waste.
Comply with the local waste disposal regulations.

Technical data

V20 ... 280
IEC / DIN EN
61643-11
U
280 V AC
C
U
N
U
P
800 V
1 kA
8/20
U
@
res
1000 V
5 kA
8/20
I
T1
imp
I
20 kA
T2
n
I
40 kA
max
I
SCCR
I
-
fi
IP code
Number of
Ports
System
TN-, TT
L – PEN
Protection
L – N
path
L – PE
N – PE
x
x ≥ 1,5 mm (0.06 in)
F1 >160 A gL / gG
F1
+
F2
F2 ≤ 160 A gL / gG
F1 ≤ 160 A
F2
2
F1
gL / gG
1.5 – 35 mm
1.5 – 35 mm
1.5 – 35 mm
Accessories
a
a ≤ 15.5 mm (0.6 in)
3 x 16 mm
5012 010
V20-...-280
C20
Class II / Type 2
255 V AC
230 V AC
≤ 1300 V
12 kA
40 kA
60 kA
50 kA
eff
100 A
IP 20 (built-in)
One-Port-SPD
TN-, TT (NPE)
-40 – +80 °C
-40 – +176 °F
5 – 95 %
N – PE
– (NPE)
– (NPE)
(AWG 16 – 2)
2
(AWG 16 – 2)
2
(AWG 16 – 2)
2
(3 x AWG 6)
2
EN
9

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis