Hitachi RPK-1.5FSN1M Installationsanleitung Seite 11

Rpk unit
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 25
DSW3: Capacity Code Setting
No setting is required, due to setting before shipment. This
dip switch is utilized for setting the capacity code which
corresponds to the Horse Power of the indoor unit.
HP
Setting position
DSW5: Refrigerant Cycle No. Setting
Setting is required. Setting position before shipment are all
OFF (Refrigerant cycle No. O)
Before shipment
Cycle No.
0
ON
ON
Setting Position
1 2 3 4
1 2 3 4
Cycle No.
4
ON
ON
Setting Position
1 2 3 4
1 2 3 4
Cycle No.
8
ON
ON
Setting Position
1 2 3 4
1 2 3 4
Cycle No.
12
ON
ON
Setting Position
1 2 3 4
1 2 3 4
CAUTION:
Adjust the vertical deflectors by hand to discharge air in the
required direction.
Do not swing 1 blade at left side and 2 blade at right side of the
vertical deflection.
Automatic Setting of louver:
When the unit operation is stopped, two air louvers are stopped
at closing position automatically.
1.0
1.5
ON
ON
1 2 3 4
1 2 3 4
ON
1 2 3 4
1
2
3
ON
ON
1 2 3 4
1 2 3 4
5
6
7
ON
ON
1 2 3 4
1 2 3 4
9
10
11
ON
ON
1 2 3 4
1 2 3 4
13
14
15
ON
ON
1 2 3 4
1 2 3 4
ELECTRICAL WIRING
DSW7: Fuse Recover
Not setting is required. Setting position before
shipment is all OFF.
In case of applying high voltage to the terminal
1,2 of TB1, the fuse on the PCB1(M) is cut.
In such a case, firstly correct the wiring to TB1
and then turn on (as showing beside).
Do not turn the air louver by hand. If moved, the
louver mechanism will be damaged! (in all units)
Horizontal
Vertical
Deflector
Deflector
5
7
ON
OFF
ON
OFF