46
| Accessories
• RVAZ4 24A Actuator 0-10V (S) — 9862
• ZTV 15-1,6 2-way valve — 9824
• ZTR 15-1,6 valve 3-way — 9673
• Duct sensor -30-70C (SAT) — 211524
Installation and connection
1. Install a duct water cooler in the duct. Connect pipes, 2/3–way valve and actuator.
Important
Do NOT use 24V DC power output from the connection board for valve actuator.
2. Connect actuator (S) to any free analog output.
3. Internal supply air temperature sensor (SAT, default connection AI2 on the main circuit board) must be replaced by a
duct temperature sensor which can be acquired as an accessory. A duct temperature sensor must be installed in the
duct before water heater: Connect duct temperature sensor in a place of internal supply air temperature sensor.
Note:
A duct temperature sensor can be connected to analog inputs 6–7 on the connection board for better
access when the internal supply air temperature sensor is disabled in the control panel.
Configuration
1. Go to Service menu
2. Enter password (default 1111)
3. Activate the actuator. Go to Components menu, select Cooler menu and select type as Water. Choose actuator
voltage type. Do advanced settings if necessary.
4. Configure connection of the duct cooler. Go to Service menu. Select Output menu. In next menu select ANALOG
tab. Select the analog output to which the water cooler is connected. Example if it is connected to AO3 on the con-
nection board, then select ANALOG OUTPUT 3 and select Y3 Cooling from the output type list.
5. Since a duct temperature sensor replaces internal supply air temperature sensor, it doesn't need to be re-configured.
Note:
A duct temperature sensor can be connected to analog inputs 6–7 on the connection board for better
access when the internal supply air temperature sensor is disabled in the control panel. Then temperature
sensor has to be re-configured as universal analog input.
6. Duct cooler and its components are now configured.
10.3.6
Change-over coil (DX)
Change-over (DX) coils can be used for both heating and cooling based on the demand.
Fig. 17 Duct cooler connections
GB