Herunterladen Inhalt Inhalt Diese Seite drucken

Specification; Figure - Megger OTS 100AF/2 Gebrauchsanleitung

Oil test sets
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Specification

Output Voltage (max.)
OTS60AF/2
OTS80AF/2
OTS100AF/2
Display
Resolution
Temperature Range
Operating
Storage
Humidity Range
Operating
Storage
External Printer Socket
Safety
E.M.C.
Supply Voltage
Fuses
Dimensions
Weight
Cleaning
60 kV (30 kV - 0 - 30 kV)
80 kV (40 kV - 0 - 40 kV)
100 kV (50kV - 0 - 50 kV)
(high voltage test frequency is 61,8 Hz)
Dot-matrix liquid crystal display giving alphanumeric information
and kV test voltage.
0,1 kV
0°C to +40°C
-40°C to +70°C
(in accordance with BS 2011 part 2)
80% RH at 40° C (non-condensing)
93% RH at 40° C, 95% RH at 25°C
(in accordance with BS 2011 part 2 )
9 pin 'D' type plug for RS232C interface
The test sets meet the requirements for IEC 1010-1 (1995)
EN61010-1 (1995)
The test sets meet EN50081-1 and EN50082-1 (1992)
220 V ± 10%, 240 V ± 10%,
110 V ± 10%, 120 V ± 10%,
(four selectable values), 50 Hz / 60 Hz.
2 x 6,3 A (F) ceramic HBC IEC 127/1, 20 mm x 5 mm
2 A (T) ceramic HBC IEC 127/5, 20 mm x 5 mm, for 220 V /240 V
4 A (T) ceramic HBC IEC 127/5, 20 mm x 5 mm, for 110 V/120 V
Mains power cord fused plug: 13 Amp fuse to BS 1362
502 mm x 464 mm x 319 mm (19
41 kg (90 lb) approx.
Wipe disconnected test set with a clean cloth dampened with
Isopropyl Alcohol (IPA)
3
in x 18
1
in x 12
1
in approx.)
4
4
2
7

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Ots 80af/2Ots 60af/2Ots100af/2

Inhaltsverzeichnis