5.1.6 MODBUS
Only available on NMT(D) MAX C.
Pump has built in Modbus client, through which we can access pump information using the RS 485 standard.
Modbus allows us to set and view:
Regulation mode settings,
Regulation parameters (power, RPM, head, flow),
Relay settings,
External control inputs settings,
Current and previews error,
Pump statistics (power consumption, run time and other).
5.1.7 RESETTING PUMP TO FACTORY SETTINGS
For resetting the pump to factory settings all three buttons must be held for 5 seconds. This way the pump will set
itself to automatic mode, delete previous height and power settings and unlock setting pump operation (if locked).
Resetting of communications module needs following steps:
1. Disconnecting power from pump,
2. Set the 10-step switch to number 9
3. Turning the pump on and off again,
4. Setting the 10-step switch to number 1,
5. Turning the pump on.
Communications module should now be set to factory settings.
8
This also sets up the right twin pump.
8
(or 8 for left twin pump),