COMMAND #37 SET PRIMARY VARIABLE LOWER RANGE VALUE
Request:
- None -
Response:
- None -
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
6 Transmitter-Specifc Command Error
7 In Write Protect Mode
9 Applied Process too High
10 Applied Process too Low
14 Warning: New Lower Range Value Pushed
16 Access Restricted
32 Busy
COMMAND #38 RESET CONFIGURATION CHANGED FLAG
Request:
- None -
Response:
- None -
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
6 Transmitter-Specifc Command Error
7 In Write Protect Mode
16 Access Restricted
32 Busy
COMMAND #39 EEPROM CONTROL
Request:
EEPROM Control Code, 8-bit unsigned integer,
0 Burn EEPROM
1 Restore Shadow RAM
2 - 249 Undefined
Response:
EEPROM Control Code, 8-bit unsigned integer,
0 Burn EEPROM
1 Restore Shadow RAM
2 - 249 Undefined
EEPROM Control Code, 8-bit unsigned integer,
0 Burn EEPROM
1 Restore Shadow RAM
2 - 249 Undefined
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
2 Invalid Selection
5 Too Few Data Bytes Received
6 Transmitter Specific Command Error
7 In Write Protect Mode
16 Access Restricted
32 Busy
COMMAND #40 ENTER/EXIT FIXED PRIMARY VARIABLE CURRENT MODE
Request:
Actual Fixed Primary Variable Current Level, IEEE 754, Units of milliamperes
Response:
Actual Fixed Primary Variable Current Level, IEEE 754, Units of milliamperes
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
3 Passed Parameter too Large
4 Passed Parameter too Small
5 Too Few Data Bytes Received
6 Transmitter Specific Command Error
7 In Write Protect Mode
11 In Multidrop Mode
16 Access Restricted
32 Busy
42/14-40-DE
Thermischer Masse-Durchflussmesser FMT500-IG (Sensyflow iG)
Anhang 2: Diagnose und HART-Kommandos
COMMAND #41 PERFORM TRANSMITTER SELF TEST
Request:
- None -
Response:
- None -
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
6 Transmitter Specific Command Error
16 Access Restricted
32 Busy
COMMAND #42 PERFORM DEVICE RESET
Request:
- None -
Response:
- None -
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
6 Transmitter-Specifc Command Error
16 Access Restricted
32 Busy
Command #43 SET PRIMARY VARIABLE ZERO
(SET PVLowFlowCutOffValue)
Request:
- None -
Response:
- None -
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
6 Device-Specifc Command Error
9 Applied Process Too High
10 Applied Process Too Low
16 Access Restricted
32 Busy
COMMAND #44 WRITE PRIMARY VARIABLE UNITS
Request:
Primary Variable Units Code, 8-bit unsigned integer
Response:
Primary Variable Units Code, 8-bit unsigned integer
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
2 Invalid Selection
5 Too Few Data Bytes Received
6 Transmitter-Specific Command Error
7 In Write Protect Mode
16 Access Restricted
32 Busy
COMMAND #45 TRIM PRIMARY VARIABLE CURRENT DAC ZERO
Request:
Externally Measured Current Level, IEEE milliamperes
Response:
Externally Measured Current Level, IEEE milliamperes
COMMAND-SPECIFIC RESPONSE CODES
0 No Command-Specific Errors
3 Passed Parameter too Large
4 Passed Parameter too Small
5 Too Few Data Bytes Received
6 Transmitter-Specific Command Error
7 In Write Protect Mode
9 Not In Proper Current Mode
11 In Multidrop Mode
12 - 15 Undefined
16 Access Restricted
32 Busy