3.4

3.4 Optimisation

Building too hot
Building is not heating up
Reference room is hot,
but individual rooms (e.g. bathroom) too cold
Reference room is not
reaching the room set temperature,
but individual rooms (e.g. bathroom) are hot
3.5 Fixed-Setpoint Regulation / Setting a Horizontal Heating Characteristic
Curve
In special cases (e.g. heating a buffer tank to a constant
temperature), it is possible to set a characteristic curve which is
independent of the external temperature. Make selections in the
menu "Settings – Heating circuit 1/2/3 – Control by – Fixed-
setpoint". The desired return set temperature can be set in the
following menu item "Fixed-setpoint Control – Return set
temp.".

4 Hot water preparation

Hot water cylinders with a sufficient heat exchanger area should
be used for DHW preparation. These must be capable of
permanently transferring the maximum heat output of the heat
pump.
Regulation is carried out using a sensor installed in the hot water
cylinder. The sensor is connected to the heat pump manager.
The temperatures attainable in heat-pump-only operation are
below the maximum flow temperature of the heat pump.

4.1 Basic Heating Using the Heat Pump

A request for domestic hot water is recognised if the current
hot water temperature < (is lower than)
Set temperature – hysteresis DHW.
A domestic hot water request ends when the hot water set
temperature is reached.
Menu
Preconfiguration
Preconfiguration
Table 4.1: Settings for basic heating of domestic hot water (user settings carried out in compliance with the operator's manual)
EN-22
1st measure
Reduce room set temperature
Raise room set temperature,
increase volume flow
Carry out hydraulic equalisation (reduce
volume flow in the reference room)
Carry out hydraulic equalisation (raise
volume flow in the reference room)
NOTE
The entered fixed-setpoint cannot be changed by pressing the buttons
Hotter ( and Colder (.
For higher hot water temperatures, the heat pump manager
offers optional control of a flange heater.
Regulation can also be carried out using a thermostat. With this
application, selective reheating using a flange heater is not
possible.
NOTE
The additional setting options for heat pumps with an additional heat
exchanger installed in the hot gas are described in Chap. 8 on p. 31.
NOTE
DHW heating can be interrupted by defrosting or by the high-pressure
safety program.
Submenu
Hot water preparation
Flange heater
2nd measure
Reduce minimum return temperature
Raise maximum return temperature
Raise minimum return temperature. 
This can lead to the room set temperature in
the reference room being periodically
overshot.
Raise maximum return temperature
Set value
Yes
No