Herunterladen Inhalt Inhalt Diese Seite drucken

Parameterizing By Download - Siemens simovert masterdrives Betriebsanleitung

Vorschau ausblenden Andere Handbücher für simovert masterdrives:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

05.2006
8.7

Parameterizing by download

Downloading with
The OP1S operator control panel is capable of upreading parameter
the OP1S
(Upread or Upload) sets from the units and storing them. These
parameter sets can then be transferred to other units by download.
Downloading with the OP1S is thus the preferred method of
parameterizing replacement units in a service case.
During downloading with the OP1S, it is assumed that the units are in
the as-delivered state. The parameters for the power section definition
are thus not transferred. If a PIN has been entered to release optional
technology functions, this is also not overwritten during downloading.
(Refer to Compendium, section "Detailed parameterization, power
section definition"). If a PIN has been entered to release optional
technology functions, this is also not overwritten during downloading.
With the "OP: Download" function, a parameter set stored in the OP1S
can be written into the connected slave. Starting from the basic menu,
the "OP: Download" function is selected with "Lower" or "Raise" and
activated with "P".
Example: Selecting and activating the "Download" function
Now one of the parameter sets stored in the OP1S has to be selected
using the "Lower" or "Raise" keys (displayed in the second line). The
selected ID is confirmed with the "P" key. Now the slave ID can be
displayed with "Lower" or "Raise". The slave ID contains various
characteristic features of the unit such as rated output, order number,
software version, etc.
The "Download" procedure is then started with the "P" key. During
download, the OP1S displays the parameter currently being written.
Example: Confirming the ID and starting the "Download" procedure
With "Reset", the procedure can be stopped at any time. If downloading
has been fully completed, the message "Download ok" appears and the
display returns to the basic menu.
Siemens AG
6SE7087-6JK50
SIMOVERT MASTERDRIVES
P
MotionControl
Download
*Menu selection
*1909199701
OP: Upread
MASTERDRIVES MC
#OP: Download
PLUS
P
Download
Download
*1909199701
*1909199701
MASTERDRIVES MC
MASTERDRIVES MC
PLUS
PLUS
Operating Instructions
P
MotionControl 00
Download
Pxxx
Parameterization
8-27

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis