5

Technical Data

Version
Safety-specific data
Gas explosion protection
Certificates
Rated operational voltage
Rated operational current
Ambient temperature
Housing material
Switching threshold
Terminals
Rated current
Rated cross section
Terminal capacity
Dimensional drawings (all dimensions in mm) - subject to alterations
144.0
120.0
104.0
82.0
30.0
37.0
Control unit 8624/1
167921 / 862460300010
S-BA-8624/1-01-en-30/07/2008
Control Unit
E II 2 G Ex mb e ia [px] [ia] IIC T4 or E II 2 G Ex mb e ia [px] IIC T4
TÜV 07 ATEX 554304
12 V / 24 V DC
24 V / 115 V AC ± 10%; 48 .. 62 Hz
230 V AC + 8.5 / - 10%; 48 .. 62 Hz
250 V AC + 5 / -15 %; 48 .. 62 Hz
250 mA at 12 / 24 V DC
300 mA at 24 V AC
60 mA at 115 V AC
30 mA at 230 / 250 V AC
- 30 °C ( T
( + 60 °C
amb
Epoxy resin, glass-fibre reinforced, black, antistatic
of the output relay according to DIN VDE 0435:
Contact potential
Type of
current
250 V
AC
240 V
AC
24 V
DC
30 V
DC
32 A for rated cross section and T
2
4 mm
(12 AWG)
2
0.2 .. 4 mm
(24 .. 12 AWG)
75.0
30.0
0.5
23.0
51.0
max. current
Power factor cos p
value
6 A
1
3 A
0.3
6 A
2.5 A
( 40 °C
a
90.0
06078E00
Control unit Ex p
8624/1
Technical Data
Service category
L/R
AC-15
0 ms
DC-13
50 ms
5

Werbung

Kapitel

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

8624/1

Inhaltsverzeichnis