MANUAL MODE FOR EVACUATION PROCEDURE

Password management
Insert password: user = 1502
Press enter to continue.
Main menu
Use arrows up/down to access the necessary masks.
Select "B. Inputs/Outputs" and press enter.
Inputs/Outputs
Select "Manual management" and press Enter to continue
Use this function ONLY to manually open EC1 and
EC3 valves during evacuation of the unit
I/O Manual
Select "Analog outputs" and press Enter to continue
Press enter to enable L1-Suction
Press enter to enable L1-Discharge
Use arrows and enter to set the timeout (15 min). Once
the specified time has been reached, both L1-Suction and
L1-Discharge manual management will be disabled.
Once the evacuation procedure is done, either wait
for the timeout to end or go back to this menu to
disable manual management
Press enter to continue.
Manual management of HPV (EC1) valve
Use this function during evacuation of the unit for
both MT and LT models.
change to 100 %.
Manual management of RPRV (EC3) valve.
function during evacuation of the unit, only for MT
models.
Use arrows and press enter to change to 100 %.
WARNING: do not operate EC3 on LT models, risk
of compressor starting.
Press escape to go back to start menu.
Use arrows and press enter to
Use this
78