Settings
CAUTION
Current sensor function / simulation
The use of the current sensor function and the simulation in safety applications can result in undesirable operating states.
The use of both functions is not permitted in safety applications.
Operation/configuration
While operating/configuring, ensure that the technical data of the temperature transmitter in the respective device version is
adhered to.
Checking the safety function
We recommend for both transmitters:
● Check the status for warnings and alarms.
● Check the upper and lower alarm current values.
● Perform a 2-point calibration.
● Check the measuring accuracy that must be in the range of ± 2% for the safety function. Check the measuring accuracy,
e.g. with a sensor calibration.
● Check triggering of the safety function.
Note
Configuration changes in SITRANS TR300 not protected by passwords
If there is no password protection, you may have to deal with undesirable changes in the configuration of the device.
We recommend that you enable password protection for your device after checking the safety function.
Behavior in case of faults
Repairs
Defective devices should be sent in to the repair department with details of the fault and the cause. When ordering
replacement devices, please specify the serial number of the original device. The serial number can be found on the rating
plate.
The address of the responsible SIEMENS repair center, contacts, spare parts lists, etc. can be found on the Internet.
18
Functional safety for SITRANS TR200/TR300
A5E03263689-02, 08/2010