06.2006
7.1.2

Power connections for units with a width of 135 mm and 180 mm

X3 - DC link bus
The DC link bus module serves to supply the unit with electrical energy.
module
Connectable cross-section: "Electro-plated copper" 3x10 mm, rounded
off according to DIN 46433
Bar 1 is at the front when installed.
Table 7-3
X2 – Motor
The motor connection is to a terminal block at the bottom of the unit.
connection
≤ 18.5 kW
PE
U2
V2
W2
Connectable cross-section:
Housing width 135 mm: 10 mm² (AWG 8), stranded
Housing width 180 mm: 16 mm² (AWG 6), stranded
Viewed from the front, Terminal PE is at the left.
Table 7-4
The motor cables must be dimensioned in accordance with VDE 298,
Part 2.
After installation of the connector, the shield of the motor cable must be
fixed to the shield plate through a large surface area.
Siemens AG
6SE7087-6KP50
SIMOVERT MASTERDRIVES
Bar
Designation
3
PE3
Protective conductor connection
2
D / L-
1
C / L+
DC link busbars
Terminal
Meaning
PE
Protective conductor connection
U2 / T1
Phase U2 / T1
V2 / T2
Phase V2 / T2
W2 / T3
Phase W2 / T3
Motor connection
Operating Instructions
Meaning
DC link voltage -
DC link voltage +
Range
3AC 0 V - 480 V
3AC 0 V - 480 V
3AC 0 V - 480 V
Connecting-up
Range
DC 510 - 650 V
DC 510 - 650 V
7-7