Function
7.5.
interfaces of the positioner
Input for
set-point value *
4 ... 20 mA **
0 ... 20 mA
Binary input
24 V DC
Communications
interface
* or optionally AS interface bus connection
** Default setting
Fig. 5:

Interfaces of the positioner

The positioner Type 8791 is a 3-wire device, i.e. the power (24 V DC) is supplied separately from the set-
point value signal.
Input for nominal position value (4 – 20 mA corresponds to 0 – 100%)
(depends on the position of DIP switch 1).
Binary input
When applying voltage of > 12 V, SAFEPOS will be activated, i.e. the valve is moved into the safety position.
Analog position feedback (optional)
The position of the valve can be relayed to the PLC via an analog 4 – 20 mA output (4 – 20 mA corresponds to
0 – 100%).
Positioner
Operation
note:
Optional inputs and outputs
are illustrated by dotted lines
Analog position
feedback
(optional)
Initiator 1 / Initiator 2
24 V PNP NO
(optional)
english
21