7.2.
before installation
Installation position:
Installation can be in any position.
Preferably: Actuator upright
→
Prior to installation check pipelines for dirt and, if
required, clean.
Dirt filter: To ensure that the safety shut-off device func-
tions reliably, install a strainer (≤ 500 µm) in front of the
valve inlet.
7.3.
installation
→
Hold the device with a suitable tool (open-end wrench)
on the housing and screw into the pipeline.
note!
Caution risk of breakage!
•
Do not use the coil as a lifting arm.
→
Observe direction of flow:
The arrow on the housing indicates the direction of flow
English
16
Note the voltage and current type as specified on
the rating plate.
→
Tighten cable plug (for permitted types see data sheet),
observing max. torque 1 Nm.
→
Check that seal is fitted correctly.
→
Connect protective conductor and check electrical
continuity between coil and housing.
English
18
7.4.
Electrical connection of the
cable plug
Danger!
Risk of injury due to electrical shock!
•
Before reaching into the device or the equipment,
switch off the power supply and secure to prevent
reactivation!
•
Observe applicable accident prevention and safety
regulations for electrical equipment!
If the protective conductor is not connected, there is a
risk of electric shock!
•
Always connect protective conductor.
•
Check electrical continuity between coil and housing.
Seal
Authorized cable plug
e.g. Type 2508 or other suitable
cable plug in accordance with DIN
ISO 175301-803 Form A
8.
mainTEnancE,
TrOublEshOOTing
8.1.
safety instructions
Danger!
Risk of injury from high pressure in the equipment!
•
Before loosening the pipes and valves, turn off the
pressure and vent the pipes.
Risk of injury due to electrical shock!
•
Before reaching into the device or the equipment,
off the power supply and secure to prevent reactivation!
•
Observe applicable accident prevention and safety
regulations for electrical equipment!
Warning!
Risk of injury from improper maintenance!
•
Maintenance may be carried out by authorized techni-
cians only and with the appropriate tools!
Risk of injury from unintentional activation of the
system and an uncontrolled restart!
•
Secure system from unintentional activation.
•
Following maintenance, ensure a controlled restart.
Type 6213 EV
max. 1 Nm
English
17
17
switch
English
19
19