Installation Instruction
UNI slip on flange
Micropilot FMR20, FMR50, FMR56
EA01103F/00/A2/02.16
71338272
Instruction is valid for the following spare part sets:
Order number
Original Spare part set
UNI slip on flange 3"/DN80/80, horn 80 mm
71162777
UNI slip on flange 4"/DN100/100, horn 100 mm
71162781
We recommend that the Installation Instructions be kept with the packaging at all times.
Designated use
The spare part set and Installation Instruction are used to replace a faulty unit with a functioning unit of the same type.
Use genuine parts from Endress+Hauser only.
Only original spare part sets, intended by Endress+Hauser for the measuring device, shall be used. 
The verification has to be done via W@M Device Viewer this procedure is explained below.
For some devices there is an overview of the correct spare part set inside the connection compartment cover.
If the spare part is listed there, the verification is not required.
1.
www.endress.com/deviceviewer
2.
Ser. No.:12345
Authorized personnel to carry out repairs
Authorization to carry out a repair depends on the approval of the measuring device. The table shows the respective group of persons for each.
The person who carries out the repair is responsible for safety during the work, the quality of work completed and safety of the device
after repair.
Approval of the measuring device
Without approval
With approval (e.g. IECEx)
1 = Trained customer technician, 2 = Service technician authorized by Endress+Hauser, 3 = Endress+Hauser (send measuring device back to manufacturer)
3.
=
?
4.
Usage
Micropilot FMR20, FMR50, FMR56
Micropilot FMR50, FMR56
1.
www.endress.com/deviceviewer
Enter the serial number (Ser. No.), search for product data and click on
2.
"spare parts".
List of all spare parts suitable for the instrument.
3.
Check the order number of the spare part.
4.
Does the order number of spare part correspond to the order number in
the spare part list?
YES, the spare part can be used.
NO, the spare part may not be used.
Group of persons authorized to
carry out repairs on FMR20
1, 2, 3
1, 2, 3
71338272
roup of persons authorized to carry
out repairs on FMR50, FMR56
2, 3
2, 3

Werbung

loading

Inhaltszusammenfassung für Endress+Hauser FMR50

  • Seite 1 FMR50, FMR56 Without approval 1, 2, 3 2, 3 With approval (e.g. IECEx) 1, 2, 3 2, 3 1 = Trained customer technician, 2 = Service technician authorized by Endress+Hauser, 3 = Endress+Hauser (send measuring device back to manufacturer)
  • Seite 2: Safety Instructions

    • Threads (e.g. of the cover for the electronics and terminal • In the case of measuring devices in custody transfer, the custody compartment), which have been prepared by Endress+Hauser with transfer status no longer applies once the lead seal has been removed.
  • Seite 3 UNI slip on flange Micropilot FMR50, FMR56 Tool list 3 mm, 8 mm T10, 0.5 Nm Lubrication grease 1.5 Nm-GT19 1.5 Nm-GT19 5 mm (tool is attached) (Syntheso Glep1) 2.5 Nm-GT18,GT20 2.5 Nm-GT18,GT20 Warning! Before dismounting the main electronic module de-energize the instrument (e.g. disconnect the terminals). ...
  • Seite 4 UNI slip on flange Re-assembly 8 mm GT18: 2.5 Nm GT19: 1.5 Nm GT20: 2.5 Nm Flange_2 Flange_2 HF_FMR5x_6 HF_FMR5x_7 0.5 Nm HF_FMR5x_8 HF_FMR5x_9 Re-assembly of all other parts is carried out in reverse order, see chapter "Replacing the UNI slip on flange", steps 5 -> 1. Endress + Hauser...
  • Seite 5 Personenkreis FMR20 Personenkreis FMR50, FMR56 ohne Zulassung 1, 2, 3 2, 3 mit Zulassung (z.B. IECEx) 1, 2, 3 2, 3 1 = Ausgebildete Fachkraft des Kunden, 2 = Von Endress+Hauser autorisierter Servicetechniker, 3 = Endress+Hauser (Messgerät an Hersteller zurücksenden)
  • Seite 6: Sicherheitshinweise

    • Die in der Betriebsanleitung aufgeführten Hinweise zum Transport – Mit den jeweiligen Einsatzbedingungen der Geräte vertraut. und zur Rücksendung beachten. – Bei Ex-zertifizierten Messgeräten zusätzlich im Explosionsschutz • Bei Fragen kontaktieren Sie bitte Ihre zuständige Endress+Hauser ausgebildet. Serviceorganisation. Micropilot FMR20 Werkzeug Es ist kein Werkzeuge nötig.
  • Seite 7 UNI Überwurfflansch Micropilot FMR50, FMR56 Werkzeugliste 3 mm, 8 mm T10, 0,5 Nm Schmierfett 1,5 Nm-GT19 1,5 Nm-GT19 (Werkzeug 5 mm (Syntheso Glep1) 2,5 Nm-GT18,GT20 2,5 Nm-GT18,GT20 beiliegend ) Warnung! Vor dem Ausbau des Hauptelektronikmoduls das Gerät spannungsfrei schalten (z.B. durch Abziehen der Anschlussklemmen)....
  • Seite 8 UNI Überwurfflansch Zusammenbau 8 mm GT18: 2.5 Nm GT19: 1.5 Nm GT20: 2.5 Nm Flange_2 Flange_2 HF_FMR5x_6 HF_FMR5x_7 0.5 Nm HF_FMR5x_8 HF_FMR5x_9 Der weitere Zusammenbau erfolgt in umgekehrter Reihenfolge, siehe Kapitel "Ausbau UNI Überwurfflansch", Handlungsschritte 5 -> 1. Endress + Hauser...

Diese Anleitung auch für:

Fmr20Fmr56