Lower limit of Zone1 total chilled water outlet temp. (COOL)
(The set temp. of Zone1 is low of 5℃, it will show " Verify that 25%
antifreeze has been added")
Upper limit of Zone2 total chilled water outlet temp. (HEAT)
Upper limit of Zone1 total chilled water outlet temp. (HEAT)
Upper limit of tank temp. (DHW)
Interface type
Anti-freezing temp. protection
Limit of defrosting entry temp.
Defrost control parameters
Defrosting method selection
Defrost maximum time interval
Cooling startup temp. deviation
Heating startup temp. deviation
Cooling shutdown temp. deviation
Heating shutdown temp. deviation
DHW startup temp. deviation
DHW shutdown temp. deviation
The Temperature Variation rate of startup
Inlet water temp. change value
Outlet water temp. change value
Time of system startup interval
Time of system standby interval
Water system type
Solar
Travel Time of Mixing Valve
DHW
Tank temp. offset
Opening time of Pump
Closing time of Pump
Tabelle 4 -Funktionen der Außenanlage, die vom Benutzer festgelegt wurden
Funktionen
Capacity regulation of system A
Capacity regulation of system B
Chilled water outlet temp. offset (COOL)
Chilled water outlet temp. offset (HEAT)
Chilled water inlet temp. offset (COOL)
Chilled water inlet temp. offset (HEAT)
Ambient temp. offset
Manual defrost of sys A
Manual defrost of sys B
Klicken Sie auf das Symbol "PASSWORD SETTING", um zur Konfigurationsmenü der Anlage zu gelangen. Sie
-5℃~10℃
35℃~60℃
35℃~60℃
35℃-58℃
Central controller/PC monitoring
-30℃~9℃
7℃~18℃
0.00~2.00
Asynchronous/Synchronous
1h~10h
0℃~5℃
0℃~5℃
0℃~5℃
0℃~5℃
0℃~5℃
0℃~5℃
0℃~5℃
0℃~5℃
0℃~5℃
1s~300S
1s~300S
Closed/Open
On/Off
30~240S
On/Off
-10~10℃
5min~60min
0min~60min
Bereich der Parameter
On/Off
On/Off
-10℃~10℃
-10℃~10℃
-10℃~10℃
-10℃~10℃
-10℃~10℃
Enable/Cancel
Enable/Cancel
37