Technical Data
Description and order number:
Power supply:
Protection:
Power consumption:
Operating temperature:
Selectable light value :
Angle of detection:
Height of assembly:
Supply and load connections:
Control terminals:
Load capacity of the control output:
Wiring:
Load capacity of the control output:
Decline period of control potential:
Switch off delay time const.light control:
Lagging time if no motion is recognized:
Parallel connection of controls:
Protective class, protective system:
Max. cable length :
Terminals:
Construction:
Contamination level:
Dimensions:
Weight:
Designation:
*
Number of connectable electronic ballasts with 15 m cable of 1,5 mm² from the distribution rack to the
MSD and further 20 m to the midst of the load circuit (impedance approx.800 mΩ). With greater cable di-
ameters or shorter wires the permissible load would be reduced (e.g at an impedance of 400 mΩ by
20%).
page 14/16
Multi-sensor dimmer, Type MSD, Order-No.: 50.13.500
Multi-sensor dimmer, Type MSD/K, Order-No.: 50.13.501 (with 1,5
m UV-resistant cable)
230V~ 50/60 Hz, DC not permitted (would damage the MSD)
external through 6A MCB or fuse
approx. 2 W
0° C.....+50° C
approx..15-1500 lux (direct at the control)
approx. 100° (photosensor and motion sensor, combined in the
MSD)
2.5 m – 3.0 m (optimum height for motion detection)
L,N, activated L (↑)
+/- (1..10V of the electronic ballasts or transformers), B (connection
for the parallel wiring of the motion indication)
Base insulation according to IEC 664 (10/92), no protective extra
low-potential
100mA (for approx. 100 electronic ballasts or transformers with 1-
(please refer to manufacturer's specification), 3 mA active for Al-
tenburger dimmers (3 dimmers of any load capacity up to 8KW)
please refer to wiring diagrams – in case of miswiring, malfunc-
tion or damage possible
5A resistive load
⇒ 30p* elec. bal. 1lamp 18W, 20 p* elec. bal. 2lamps 18W
30p* elec. bal.1lamp 36W, 20 p* elec. bal. 2 lamps 36W
20p* elec. bal.1lamp 58W, 10 p* elec. bal.2 lamps 58W
approx. 10-30 seconds (depending on the control difference)
10 minutes
adjustable between 1 and 30 minutes+10min until switch off
totally max. 6 MSD (motion detection through the controls)
II (protective insulation), IP 20
100 m (control wires 0.5 mm², load and supply wires 1.5 mm²)
Screw-type terminals for single-wires or litz wires 0.3mm² – 1.5
mm² or with 1.5 m cable
Plastic housing for mounting on ceilings or lamp fixture louvres
2 (dry, non-conducting, according to IEC664, 10/92)
W x H x D = 58.5 x 70.5 x 42 mm
approx. 150 g
CE
Operating instruction Multi Sensor Dimmer MSD
Altenburger Electronic GmbH