SICK LFP inox Betriebsanleitung Seite 81

Tdr-füllstandsensor

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

LFP Inox
Parameter
AutCal
Q1MENU, Q2MENU
SPx
RPx
FH2
FL2
OUx
SimQx
TYP2
QAMENU
QAHIGH
QALOW
QAPOL
QATYP
8014485/YE12/2014-08-20 © SICK AG • Level sensors • Germany • Subject to change without notice
6 Menu overview
Description
See chapter „2 Commissioning the LFP"
See chapter „3 Configuring the switching outputs"
Switching point, switching output 1 or 2 (SPx > RPx)
Reset point, switching output 1 or 2
Note: This stops appearing when the switching output is set to Error or Window in
the OU2 menu.
Upper threshold (high) window function, switching output 2 (FHx > FLx)
Lower threshold (low) window function, switching output 2
Note: This stops appearing when the switching output is set to Error in the OU2
menu.
Switching function, switching output
Qx-Hno = Hysteresis function, normally open
Qx-Hnc = Hysteresis function, normally closed
1)
Qx-Fno = Window function, normally open (function only available for Q2)
Qx-Fnc = Window function, normally closed (function only available for Q2)
Qx-Eno = Error signal, normally open (function only available for Q2)
Qx-Enc = Error signal, normally closed (function only available for Q2)
If Qx is used as an error signal, SPx/FHx and RPx/FLx are hidden in the menu.
See chapter „5.3 Testing the configuration"
Qx-PNP = Switching output in PNP circuit
Qx-NPN = Switching output in NPN circuit
Qx-Drv = Switching output executed in Push/Pull function
See chapter „4 Configuring the analog output"
Input of the filling level in mm for 20 mA/10 V signal (QAHIGH > QALOW)
Input of the filling level in mm for 4 mA/0 V signal
The analog output signal can be inverted
QA-Nrm = Analog output signal as configured
QA-Inv = Analog output signal is inverted: QAHigh 4 mA/0 V and QALow
20 mA/10 V
Setting of the output signal
4-20 mA
0-10 V
Auto V = Qa operated with voltage output of 0 to 10 V
Auto A = Qa operated with current output of 4 to 20 mA
Auto? = Automatic signal detection based on the existing load
During a menu query, either 4-20 mA or 0-10 V is displayed.
EN
Operating instructions
81