BONFIGLIOLI Vectron ACTIVE Betriebsanleitung Seite 30

Fernwartungskit
Vorschau ausblenden Andere Handbücher für Vectron ACTIVE:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

8
8.1
By default, the modem supplied with the teleservice kit is configured for teleservice of
the frequency inverters of either the ACT/ACU OR the VCB series of devices. The
modem is set up such that it can be connected to both the frequency inverter and the
PC.
In the factory configuration, the modem can be used for communication with
frequency inverters
If the modem on the plant side is to be used for a device series which deviates from
the modem configuration, the factory configuration must be changed.
The individual configuration settings as well as the corresponding procedures are
explained in the following.
The configuration is based on standardized commands for Hayes-compatible modems
(AT commands).
8.1.1
Note:
8.1.2
In the terminal program of the PC, the following connection settings must be made:
For information on how to set these parameters, please refer to the operating
instructions or the help function of your terminal program. After the connection has
been established successfully, enter the following AT commands via the terminal
program:
Confirm each command by pressing the Enter key. After processing the command
successfully, the modem signals "OK" in the terminal program window. For more
information, refer to the modem operating instructions.
11/07
13
All manuals and user guides at all-guides.com
Annex
Configuration of Modem
of the ACT and ACU series of devices OR
of the VCB series of devices
Preparations
You need a PC
with an unoccupied serial interface and
a terminal program (e.g. Windows Hyper Terminal).
Connect the modem to the PC using the serial interface cable.
During the configuration, no other application which uses the same
interface (COM port) may be active on the computer.
Modem Configuration for Remote Connection to
ACT/ACU - Frequency Inverters
Baud rate
19200 bits per second
Data bits
7
Parity
even
Stop bits
1
Flow control
Hardware
at &F0
-> Reset to factroy default
at Y0
-> Select NVRAM Nr. 0
at s0=1
-> selected modem answers (after 1
at &b1
-> The baud rate of the serial interface is set to a fixed value.
at &w0
-> Save the current configuration in the modem memory.
Symbol line in the "hyperterminal"
st
ring tone)