Operating instructions
Output expander module
1.6 Warning about misuse
In case of inadequate or improper use or manipulations of
the output expander module, personal hazards or damage
to machinery or plant components cannot be excluded.
The relevant requirements of the standards EN 1088 and
EN ISO 13850 must be observed.
1.7 Exclusion of liability
We shall accept no liability for damages and malfunctions resulting from
defective mounting or failure to comply with this operating instructions
manual. The manufacturer shall accept no liability for damages result-
ing from the use of unauthorised spare parts or accessories.
For safety reasons, invasive work on the device as well as arbitrary re-
pairs, conversions and modifications to the device are strictly forbidden;
the manufacturer shall accept no liability for damages resulting from
such invasive work, arbitrary repairs, conversions and/or modifications
to the device.
The safety-monitoring module must only be used when the enclosure is
closed, i.e. with the front cover fitted.
2. Product description
2.1 Ordering code
This operating instructions manual applies to the following types:
MIRO SAFE+ E 24
Art.-No. 3000-33113-3020075
This device is designed as output expander module. The
safety function is only realised in conjunction with the basic
device. To this effect, the device must be connected in
accordance with the wiring example!
Only if the information described in this operating instruc-
tions manual are realised correctly, the safety function and
therefore the compliance with the Machinery Directive is
maintained.
2.2 Special versions
For special versions, which are not listed in the order code below 2.1,
these specifications apply accordingly, provided that they correspond to
the standard version.
2.3 Destination and use
The output expander modules for integration in safety circuits are
designed for fitting in control cabinets. They are used for the safe evalu-
ation of the signals and the safe contact multiplication of an upstream
safety-monitoring module.
The safety function is defined as the opening of the enabling circuits
13-14, 23-24, 33-34 and 43-44 when the supply voltage A1-A2 is dis-
connected. The safety-relevant current paths with the outputs contacts
13-14, 23-24 and 33-34 meet the following requirements under obser-
vation of a PFH value assessment (also refer to chapter 2.5 "Safety
classification"):
– Control category 4 – PL "e" to DIN EN ISO 13849-1
– corresponds to SIL 3 to DIN EN 61508-2
– SILCL 3 to DIN EN 62061
To determine the Performance Level (PL) of the entire safety function
(e.g. sensor, logic, actuator) to DIN EN ISO 13849-1, an analysis of all
relevant components is required.
8
MIRO SAFE+ E 24_en.indd 8
Art.-No. 3000-33113-3020075
2.4 Technical data
General data:
Standards:
Climate resistance:
Mounting:
snaps onto standard DIN rail to EN 60715
Terminal designations:
Material of the housings:
Material of the contacts:
Weight:
Start conditions:
Feedback circuit (Y/N):
Pull-in delay:
Drop-out delay:
Mechanical data:
Connection type:
Cable section:
Connecting cable:
With removable terminals (Y/N):
Mechanical life:
Electrical life:
Resistance to shock:
Resistance to vibrations to EN 60068-2-6:
Ambient conditions:
Ambient temperature:
Storage and transport temperature:
Protection class:
Air clearances and creepage
distances to IEC/EN 60664-1:
EMC rating:
Electrical data:
Contact resistance in new state:
Power consumption:
Rated operating voltage U
:
e
Frequency range:
Max. fuse rating of the operating voltage:
Monitored inputs:
Short-circuit recognition (Y/N):
Wire breakage detection (Y/N):
Earth leakage detection (Y/N):
Number of NO contacts:
Number of NC contacts:
Conduction resistance:
Outputs:
Number of safety contacts:
Number of auxiliary contacts:
Number of signalling outputs:
Switching capacity of the safety contacts:
max. 250 V, 6 A ohmic (inductive in case of
appropriate protective wiring); min. 10 V / 10 mA
Switching capacity of the auxiliary contacts:
Protection of the safety contacts:
Fuse rating for the auxiliary contacts:
Safety fuse 2.5 A quick blow, 2 A slow blow
Utilisation category to IEC/EN 60947-5-1:
Dimensions H x W x D:
The data specified in this manual are applicable when the
component is operated with rated operating voltage U
EN
MIRO SAFE+ E 24
IEC/EN 60204-1, EN 60947-5-1;
EN ISO 13849-1, IEC 61508
EN 60068-2-78
EN 60947-1
glass-fibre reinforced
thermoplastic, ventilated
AgSnO, self-cleaning, positive drive
215 g
Automatic
yes
≤ 30 ms
≤ 35 ms
plug-in cage clamps
min. 0.25 mm² / max. 2.5 mm²
rigid or flexible
yes
10 million operations
Derating curve available on request
10 g / 11 ms
10 ... 55 Hz,
amplitude 0.35 mm
– 25 °C ... +45 °C
– 40 °C ... +85 °C
Enclosure: IP40
Terminals: IP20
Clearance: IP54
4 kV/2 (basic insulation)
to EMC Directive
max. 100 mΩ
max. 1.0 VA
24 VDC –15% / +20%,
residual ripple max. 10%,
24 VAC –15% / +10%
50 / 60 Hz
F1: T 1.0 A / 250 V
no
Yes
Yes
0
0
max. 40 Ω
4
2
0
13-14; 23-24; 33-34; 43-44:
51-52; 61-62:
24 VDC / 2 A
external (I
= 1000 A)
k
to EN 60947-5-1
8 A quick blow, 6 A slow blow
external (I
= 1000 A)
k
to EN 60947-5-1
AC-15: 230 VAC / 6 A
DC-13: 24 VDC / 6 A
100 mm x 22,5 mm x 121 mm
±0%.
e
11.06.2012 13:53:28