Installation Guide
1
Introduction
In this installation manual, the phrase "heating cable" refers
to heating cables in readymade lengths; heating cables
on drums; heating cables on mesh; and preshaped taped
heating cables.
2
Safety instructions
Heating cables must always be installed according to local
building regulations and wiring rules as well as the guide-
lines in this installation manual.
• De-energize all power circuits before installation and service.
• Residual current device (RCD) protection is required. RCD trip
rating is max. 30 mA.
• The screen from each heating cable must be earthed in
accordance with local electricity regulations
• Heating cables must be connected via a switch providing
all pole disconnection.
• The heating cable must be equipped with a correctly sized
fuse or circuit breaker according to local regulations.
• Never exceed the maximum heat density (W/m or W/m²)
for the actual application.
3
Installation guidelines
• It is not recommended to install heating cables at tem-
peratures below -5°C.
• Heating cable bending diameter must be at least 6 times
the cable diameter. Do not bend connections.
4
Mechanical class
M1— For use in applications with low risk of mechanical
damage according to IEC 60800:2009, e.g. installed on even
surfaces and embedded in screeds with no sharp objects.
M2 — Can be used in applications with high risk of mecha-
4
Heating cables
To get the full installation guide, warranty registration,
product information, tips & tricks, addresses, etc.
visit www.devi.com and www.gb.manuals.devi.com.
• Strongly recommended to use the heating cable together with
an appropriate thermostat to secure against overheating.
• Caution! Do not use M1 classified cables in areas subject
to high mechanical loads or impact, such like outdoor ap-
plications, on steel reinforcing grids, in concrete with sharp
stones, roof and gutters, etc.
The presence of a heating cable must
• be made evident by affixing caution signs in the fuse box
and in the distribution board or markings at the power
connection fittings and/or frequently along the circuit line
where clearly visible (tracing).
• be stated in any electrical documentation following the
installation.
• Free end from cold lead must be protected by installer to avoid
water from coming in.
nical damage according to IEC 60800:2009.
C — High mechanical strength according to IEC 60800:1992.
MMM — Marking for high mechanical protection class ac-
cording to NF C 32-330:2002.
DEVI