Tip:
Further instructions for surface mounting or mounting using adapters are supplied with

the respective surface-mounted frame or adapter.
Preparation
Note:
We recommend securing the panel, since in rare cases the panel must be completely

disconnected from the power supply.
Necessary accessories for the installation of the panel:
Flush-mounted box (PNX12-10004) or surface-mounted frame (PNX12-10005)
Glass cover
Power supply unit 24 V DC for DIN rail (PNX12-10010) (recommended)
or
Power supply unit 24 V DC for the flush-mounted box (PNX12-10011)
Flush-mounted installation
Tip:
Choose the installation height of the panel according to the height of the primary user

so that the top edge of the panel is at his/her eye level. A slightly lower screen prevents fatigue
of the arms during operation.
Installation in brickwork
1.
Make a recess of H x W: 194 x 252 mm in the wall. Therefore, use the template provided.
The flush-mounted box must later be flush with the plastered wall.
2.
Depending on the cable position, press the circular plates at the top or bottom out of the
box and insert the supplied self-sealing grommets to prevent damage to the cable.
3.
When inserting the flush-mounted box, route the supply and communication cables (Ether-
net, KNX) through different holes in the flush-mounted box to avoid possible interference.
4.
Use the template as a splash guard during the filling of the edges.
Flush-mounted installation