Wiring diagram
Connect terminals " A1 " and " A2 " to the supply voltage U
IEC 60364-4-43, i.e. the connections are to be protected against short circuit
by means of a protective device (a 6 A fuse is recommended). Devices for pro-
tection against short-circuit in conformity with IEC 0100-430 for the coupling
of terminals " L1/+ " / " L2/- " to the IT system to be monitored can be omitted if
the wiring is carried out in such a manner as to reduce the risk of a short-circuit
to a minimum.
Only one ISOMETER® may be controlled via a test/reset button. It is not allo-
wed to use a parallel connection of several test or reset inputs for combined
testing of ISOMETER®s.
24
E
L1/+
L2/
Test / Reset
T/R
Fig. 7.2: Wiring diagram of isoES425
U
S
KE
A1
A2
E
KE
A1 A2
L1/+
L2/-
k
ON
AL1
AL2
isoES425
k
<
ISOMETER
T
R
MENU
14
24
11
R
on
B
T/R
A
off
K1
K2
R
B
A
14
24
11
isoES425_D00214_00_Q_DEEN/08.2017
according to
s
L1/+
L2/-
L3
PE
COM465IP
RS-485