Obj
Object name
Time factor for light 1 basic
27
illumination ON period
This object is only visible if the "Basic Illumination ON" parameter is set to
"Yes" in the "Basic Illumination" parameter window. The group address
linked with this object can be used for changing the ON period for basic il-
lumination (in minutes) via bus. Basic illumination is switched OFF once the
ON period expires. Any value received outside the permissible range of 1 to
255 is rejected. This object can also be used at any time for requesting the
current ON period for timed basic illumination, also after making a change
via ETS or IR remote control.
28
HVAC output
This object is only visible if the "HVAC Output" parameter is set to "active" in
the "General Settings" parameter window.
This object must be linked with the presence input of the room-temperature
regulator used for switching the room mode between "comfort mode" and
"energy-saving mode". The group address linked with this object is used for
sending the HVAC status via bus to the actuator, with it also being possible
to request this from the detector.
29
Disable HVAC output
This object is only visible if the "HVAC Output" parameter is set to "active" in
the "General Settings" parameter window and if the "Disable HVAC output"
parameter is not set to "No" in the "HVAC output" parameter window.
The "Disable HVAC output" parameter is also used for selecting whether to
perform disabling on receiving a value of "1" or on receiving a value of "0".
When the "HVAC output" is disabled, the detector does not send any tel-
egrams for governing the mode of HVAC control.
HVAC output disabling
30
status
This object is only visible if the "HVAC Output" parameter is set to "active" in
the "General Settings" parameter window and if the "Disable HVAC output"
parameter is not set to "No" in the "HVAC output" parameter window.
The group address linked with this object is sent via the bus to indicate (or it is
possible to enquire via the bus) whether the HVAC output is disabled (HVAC
output disabling status = ON) or not.
Time factor for HVAC
31
switch-ON delay
This object is only visible if the "HVAC Output" parameter is set to "active" in
the "General Settings" parameter window.
The group address linked with this object is used for receiving the switch-ON
delay (in minutes) via bus, during which the room-temperature control system
is not switched to comfort mode after persons are already present in the
room. This object can also be used for requesting the latest HVAC stay-ON
time at any time, also after making a change via ETS or IR remote control.
Note: The value "0" indicates that the switch-ON delay in "room surveillance
mode" is set by the detector automatically.
Time factor for HVAC
32
stay-ON time
This object is only visible if the "HVAC Output" parameter is set to "active" in
the "General Settings" parameter window.
The group address linked with this object is used for receiving the stay-ON
time (in minutes) via bus, this being the time for which the room temperature
control system is to remain switched to comfort mode after there is no per-
son remaining in the room. Any value received outside the permissible range
of 1 to 255 is rejected. This object can also be used for requesting the latest
HVAC stay-ON time at any time, also after making a change via ETS or IR
remote control.
Light/HVAC interconnection
33
input
This object is only visible if the "Interconnection" parameter is set to "Yes" in
the "General Settings" parameter window.
The group address linked with this object is used by the sensor for receiving
the presence status of the slave via the bus and, if applicable, linked with the
presence status of further slaves as well as the sensor via a logical OR func-
tion. This input is used for extending the range of the light output.
Function
DP type
Flag
5,005
1...255
CRWT
(8 bits)
1,001
ON/OFF
CRT
(1 bit)
1,001
ON/OFF
CWT
(1 bit)
1,001
ON/OFF
CRT
(1 bit)
5,005
0...255
CRWT
(8 bits)
5,005
1...255
CRWT
(8 bits)
1,001
ON
CWT
(1 bit)
Application description for 3000-series sensors
Obj
Object name
Light/HVAC interconnection
34
output
This object is only visible if the "Interconnection" parameter is set to "Yes" in
the "General Settings" parameter window.
The group address linked with this object is used for sending the presence
status from the sensor. This output is used for extending the range of the
light output.
35
Photo-cell controller output
This object is only visible if the "Photo-Cell Controller Output" parameter is
set to "active" in the "General Settings" parameter window. This object must
be linked with the switching object of the actuator used for switching the
twilight illumination ON and OFF. The group address linked with this object is
used for sending the switching command via bus to the actuator, with it also
being possible to request the switching status from the detector.
36
Light level threshold
This object is only visible if the "Photo-Cell Controller Output" parameter is
set to "active" in the "General Settings" parameter window.
The group address linked with this object can be used via the bus for chang-
ing the photo-cell controller threshold (in lux) at which twilight illumination is
activated if the ambient light level is not sufficient and at which twilight illumi-
nation is switched OFF again when significantly exceeded.
Any value received outside the permissible range of 2 to 1000 lux is rejected.
This object can also be used for requesting the current threshold value at any
time, also after making a change via ETS.
37
Disable photo-cell controller
This object is only visible if the "Photo-Cell Controller Output" parameter is
set to "active" in the "General Settings" parameter window and if the "Disable
photo-cell controller" parameter is not set to "No" in the "Photo-Cell Control-
ler" parameter window. The "Disable Photo-Cell Controller" parameter is also
used for setting whether disabling is to take place after receiving a value of
"1" or after receiving a value of "0".
The detector sends no telegrams on light level status when the photo-cell
controller is disabled.
Photo-cell controller
38
disabling status
This object is only visible if the "Photo-Cell Controller Output" parameter is
set to "active" in the "General Settings" parameter window.
Sent via bus or retrievable via bus, the group address linked with this ob-
ject shows whether the photo-cell controller is disabled (photo-cell controller
disabling status = ON) or not.
39
8-bit scene output
This object is only visible if the "Remote Control" parameter is set to "User" or
to "Program & User" in the "General Settings" parameter window.
This object is used for sending a telegram for restoring or saving an 8-bit
scene. The number of the 8-bit scene being restored or saved is set via the
relevant parameter in the "Scene Control" parameter window.
40
Sabotage
This object is only visible if the "Sabotage" parameter is set to "active" in the
"General Settings" parameter window.
An ON or OFF telegram is sent cyclically to the group address linked to this
object while the sensor is not disconnected from the bus or if it is faulty.
- 7 -
Function
DP type
Flag
1,001
ON
CRT
(1 bit)
1,001
ON/OFF
CRT
(1 bit)
9,004
2 to 1000 lux
CRWT
(16 bits)
1,001
ON/OFF
CWT
(1 bit)
1,001
ON/OFF
CRT
(1 bit)
18,001
select/save
CRT
(8 bits)
1,001
ON/OFF
CRT
(1 bit)