Inflowing medium
LEVEL TRANSMITTER 8186 • 4 ... 20 mA/HART two-wire
Depending on the tube diameter or tube length, one or several spacers
can be mounted. With cable probes, the cable can also be strained to
avoid contact with the tube.
The max. temperature for the spacers is 250 °C (482 °F).
Keep in mind that buildup can form on the spacers. Strong buildup can
influence the measurement.
Microwaves can penetrate plastics. For process technical reasons,
plastic standpipes are problematic. If durability is no problem, then we
recommend the use of metal standpipes.
Fig. 5: Position of the spacer
1
Spacer
Note:
Measurement in a standpipe is not recommended for very adhesive
products.
Make sure that the probe is not subjected to strong lateral forces.
Mount LEVEL TRANSMITTER 8186 at a position in the vessel where
no disturbances, e.g. from filling openings, agitators, etc., can occur.
4 Mounting
1
13