running the automatic adjustment for TUNE FUNCTIONS
X.TUNE
Automatic adjustment of the positioner
PQ-LIN
Automatic linearization of the process characteristic
5)
P.TUNE
Self-optimization of the process controller
5)
The TUNE FUNCTIONS must be run for a function check of the positioner / process controller to adjust
to specific local features.
Warning!
while the TUNE FUNCTIONS is running, the valve automatically moves from its current position!
• Never run TUNE FUNCTIONS while a process is running!
• Take appropriate measures to prevent the system / positioner / process controller from being unintentionally
actuated!
noTe!
avoid maladjustment of the controller due to an incorrect compressed air supply or applied operating
medium pressure!
• Run TUNE FUNCTIONS whenever the compressed air supply (= pneumatic auxiliary energy) is available
during subsequent operation.
• Run the TUNE FUNCTIONS function preferably without operating medium pressure to exclude interference
caused by flow forces.
Figure 21:
Starting TUNE FUNCTIONS
only with process controller Type 8693 and 8793