The exhausts of the safety valves must be channelled outside to open air in compliance with the requirements below. In particular, the exhaust of safety
valve channelling must be at least 3m above ground level.
In case of breakage, the evaporator of the unit could release refrigerant into the hydraulic circuit. The installer is in charge of designing and protecting the
hydraulic circuit by a safety valve located distant from possible triggering sources.

2.4.4. WARNINGS CLEARANCE AND POSITIONING

IMPORTANT!
Before installing the unit, check the noise limits allowed in the place where it will be used.
IMPORTANT!
The unit should be positioned to comply with the minimum recommended clearances, bearing in mind the access to water and electri-
cal connections.
IMPORTANT!
If clearance distances are not maintained at installation, it could cause malfunctioning with an increase in absorbed power and a con-
siderable reduction in cooling capacity.

2.4.5. CLEARANCE AND POSITIONING

2160-2180
IOM_EQRU-SS_EQRHU-SS_2160a4350_208676_230601_ES-EN-FR-DE-IT
80
Minimum height 3m
Hmin
Danger zone
ZP
Safety valve exhaust
SVS
Valve ducting
E8
Ground level
PDC
EQRU-EQRUSS
EQRHU-EQRHUSS
mm
L1 (*)
mm
L2 (**)
mm
L3 (*)
mm
L4 (***)
1500
1500
1500
1000