Table 5 describes the parameters sensitive to the inverter and provided in the advanced menu. To exit the advanced menu, scroll
through all parameters using the central button.
Parameter
symbol
Serial
Unique serial number attributed for connectivity
Electric pump rated frequency Set the value stated
Fn
on the electric pump dataplate.
Electric pump rated current Set the value stated on
In
the electric pump dataplate.
Direction of rotation. Modify this parameter to invert
Rt
the direction of rotation.
Fm
Minimum rotation frequency of the electric pump.
FM
Maximum rotation frequency of the electric pump
Fq
Quick start frequency
SM
Numero di giri al minuto massimo dell'elettropompa.
--
Differential pressure type of sensor
H0
Maximum electric pump head.
Fc
Inverter carrier frequency
Dry running power. If you want to enable protection
against dry running, set the value of the absorbed
DR
power at Fn (normal frequency) in dry running
conditions, increased by 20%.
Time that passes between switching off one pump
ET
and switching on the other in twin systems.
Characteristic constant of the NTC resistance, used
B
for the measurement of fluid temperatures T and T1
Running time of the hydraulic circuit, it acts in an
Td
inversely proportional way on the regulating speed
in the T and DT regulations.
Bs
Parameter for setting up Booster mode
Ad
Modbus address of the device
Br
Serial communication baud rate
Pa
Type of parity control
Sb
Number of stop bits
Rd
Minimum response time
En
Modbus enabling
Table 5: Advanced menu – Sensitive inverter parameters
Home Page
Page 1.0
Description
The main settings of the system are graphically summed up on the Home Page.
The icon at top left indicates the type of regulation selected.
The icon at centre top indicates the operating mode selected (auto or economy).
The icon at top right indicates the presence of a single
icon
or
indicates which circulation pump is operating.
At the centre of the Home Page is a read-only parameter which can be chosen from a small set of
parameters on Page 8.0 of the menu.
From the Home Page it is possible to access the page for regulating the contrast of the display: hold
down the hidden button, then press and release the right button.
From the Home Page it is also possible to access the read-only menu of the inverter sensitive
parameters set in the factory: hold down the central button for 3 seconds.
The factory settings are set from Page 1.0 by holding down the left and right buttons at the same time
for 3 seconds.
The resetting of the factory settings will be notified by the appearance of the symbol
word "Default".
ENGLISH
Range
50 - 200
MCE-30
1,0 – 7,5
0 – (8/10)*Fn
(8/10)*Fn - Fn
3/10*Fn-Fn
12*Fn - 60*Fn
Ratiometric with fs = 4 bar
Ratiometric with fs = 10 bar
2.0 –fs pressure sensor
0.0 – 15.0
1-10000
0-1800
1.2, 2.4, 4.8, 9.6, 19.2, 38.4
None, Odd, Even
0-3000
Disable, Enable
or twin inverter
45
Measurement
-
MCE-55
1,0 – 13,5
0 - 1
5 - 20
--
0-80
1-247
1-2
. The rotation of the
unit
-
Hz
A
--
Hz
Hz
Hz
r.p.m.
--
m
kHz
W
s
°K
s
%
Kb/s
ms
next to the