the motor is activated at speed V (minimum or maximum, as set during configuration) by the PIR presence sensor
tripping. The motor will switch off at the end of the sensor signal, after a delay of between 3 and 20 minutes (as set during
configuration, see "Instructions for the Installer).
LL T: on this model the PCB permits one operating mode: the motor starts at speed V (minimum or maximum, as set
during configuration) on pressing the switch. Pressing the switch again will switch off the motor, after a delay of between
3 and 20 minutes (as set during configuration, see "Instructions for the Installer").

Installer instructions

For some models the installer can change the factory settings:
LL
No configuration tasks for the installer
LL TP
Factory settings
- switch-off delay (dip switch): 6 min
- switch-on delay (dip switch): 45 seconds
- automatic switch-on cycle: OFF = 0 H
- 2 speeds: position A of the jumper (fig.16)
Possible settings
- Jumper setting (fig 15a,16). The motor has two operating speeds: V1 and V2. By appropriately setting the jumpers as
described in the following table A it is possible to determine which will be the maximum and minimum speed between
V1 and V2. The timer will always act on V1.
- Dip-switch settings (fig. 17). N.B. Before making any changes to the dip-switches, disconnect the electric power supply.
It is possible to configure the time lag for switching on, switching off and the automatic switch-on cycle time (see under
Use) by appropriately setting the 6 DIP-switches as described in the following table
0 sec.
OFF
45 sec.
ON
T
A
90 sec.
OFF
120 sec.
ON
6 min.
--
10 min.
--
T
B
15 min.
--
21 min.
--
0 hr.
--
8 hr.
--
T
C
12 hr.
--
24 hr.
--
LL TP HCS
Factory settings
- switch-off delay (dip switch): 6 min
- switch-on delay (dip switch): 45 seconds
- humidity threshold: 70 %RH
- operation mode: Timer
- 2 speeds: position A of the jumper (fig.16)
Possible settings
- Jumper setting (fig 15b,16). The motor has two operating speeds: V1 and V2. By appropriately setting the jumpers as
described in the following table A it is possible to determine which will be the maximum and minimum speed between
V1 and V2. The timer will always act on V1.
- Dip-switch settings (fig. 17). N.B. Before making any changes to the dip-switches, disconnect the electric power supply.
It is possible to configure the time lag for switching on, switching off, the Relative Humidity threshold value and the
operating mode (see under Use) by appropriately setting the 6 DIP-switches as described in the following table:
40
Int. 1
Int. 2
OFF
OFF
ON
ON
--
--
--
--
--
--
--
--
DIP switch
Int. 3
Int. 4
--
--
--
--
--
--
--
--
OFF
OFF
ON
OFF
OFF
ON
ON
ON
--
--
--
--
--
--
--
--
Int. 5
Int. 6
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
OFF
OFF
ON
OFF
OFF
ON
ON
ON