Herunterladen Inhalt Inhalt Diese Seite drucken

Parameter Settings - Parker StarlettePlus-E SPS004 Benutzerhandbuch

Vorschau ausblenden Andere Handbücher für StarlettePlus-E SPS004:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 27
5
Control
QS
Main power switch
UP button: press to increase the value of a selected
parameter
DOWN button: press to reduce the value of a selected
parameter
esc
ESC button :returns to the previous level
SET button : one single press to see the alarms, press
set
for more seconds to enter Menu (Service e Factory)
(lit) Dew point correct
(Flashing) warning dew point high/low
(off) alarm dew point
(lit) Condensate drain ON
(off) Condensate drain OFF
(lit) Multiple alarms
(Flashing) Warning "maintenance"
Degree

5.1 Parameter settings

There are two levels of protection for parameters:
a) User (U): with immediate access, User-changeable;
b) Password protected Factory/Service (F/S): password required
for access; Factory-set parameters.
Condensate drain
There are two operating modes:
a) TIMED (TIm) - with draining at intervals and settable time;
in this confi guration keep pressed
work;
English
b) EXTERN (CON) - if there is an external drain.
For chosing the set proceed as follows::
Press button
Using buttons
fi rm.
Using buttons
esc
Press
to confi rm and exit.
In the same way it is possible to change interval and discharge
times of the drain.
Parameter table
Code
dON
Time ON Drain (sec.)
dOFF
Time OFF Drain( 1=10 sec.)
CHd
Confi guration drain
ALC
relay alarm/warning
OFF = relay energised for alarms/warnings
ON = relay energised only alarms
ST1 = relay energised for No alarms/warnings present
ST2 = relay energised for No alarms present
to force the drain to
set
over 5 seconds to enter on menu U.
set
and
select "CHd" and press
and
select "TIm" or "CON" .
Defi nition
De-
Min Max.
fault
5
1
12
2
TIm
TIm
ON
-
Flow Chart
set
>5 sec.
Menu
CHd
User
set
esc
TIm
CON
SPS004-SPS100
Alarms/Warnings
When an alarm is ON, the "alarm/warning code" fl ashing on dis-
play.
Multiple alarms appear in sequence. The symbol appears
to con-
set
In any case you can press
tons
and
.
Code
Description alarm / warning
---
No alarms present
HdP
Alarm High Dew point
LdP
Alarm Low Dew Point
DSE
Alarm sensor B1 faulti/disconnected
H
Warning High Dew point
60
L
Warning Low Dew point
270
esc
CON
Press
to exit.
-
Flow Chart
set
<5 sec.
Code 1
Code 2
Alarm
Alarm
Warning
Warning
esc
esc
.
to see the alarms, using the but-
Code....
Alarm
Warning
esc
.
3 / 6

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis