11. Specifications
11. Specifications
DANGER!
Danger to life due to loss of explosion protection
The non-observance of the instructions for use in hazardous areas can lead
to the loss of the explosion protection.
▶
Adhere to the following limit values and instructions.
Specifications
Permissible ambient temperature range
Climate class per IEC 654-1:1993
Maximum permissible humidity
Model T15.H
■
per IEC 60068-2-38:2009
Model T15.R
■
per IEC 60068-2-30:2005
Vibration resistance
per IEC 60068-2-6:2008
Shock resistance
per IEC 68-2-27:2009
Salt fog
per IEC68-2-52:1996, IEC 60068-2-52:1996
Condensation
Free fall
in line with IEC 60721-3-2:1997,
DIN EN 60721-3-2:1998
Electromagnetic compatibility (EMC)
per DIN EN 55011:2010, DIN EN 61326-2-3:2013,
NAMUR NE21:2012, GL 2012 VI part 7
{ } Items in curved brackets are options for an additional price, not for ATEX versions of the head mounting version and not for
T15.R rail mounting version
1) In the event of interference caused by high-frequency electromagnetic fields in a frequency range from 80 to 400 MHz, an
increased measuring deviation of up to 0,8 % is expected. During transient interferences (e.g. burst, surge, ESD) take into
account an increased measuring deviation of up to 1,5 %.
WIKA operating instructions model T15
Model T15
{-50} -40 ... +85 {+105} °C
{-58} -40 ... +185 {+221} °F
Cx (-40 ... +85 °C / -40 ... +185 °F, 5 ... 95 % r. h.)
Test max. temperature variation 65 °C (149 °F) /
-10 °C (14 °F), 93 % ±3 % r. h.
Test max. temperature 55 °C (131 °F), 95 % r. h.
Test Fc: 10 ... 2,000 Hz; 10 g,
amplitude 0.75 mm (0.03 in)
Acceleration / shock width
Model T15.H: 100 g / 6 ms
Model T15.R: 30 g / 11 ms
Severity level 1
Model T15.H: Acceptable
Model T15.R: Acceptable in vertical mounting
position
Drop height 1.5 m (4.9 ft)
EN 61326 emission (group 1, class B) and
1)
interference immunity (industrial application)
[HF field, HF cable, ESD, Burst, Surge]
EN
29