Problem
The charger is not
functioning
The battery is not
being charged fully.
The battery is
overcharged.
Battery charge
current drops to 0
when the
absorption voltage
is reached
24
Cause
The AC input voltage or frequency
is out of range.
The thermal circuit breaker has
tripped.
Incorrect charging current.
A defective battery connection.
The absorption voltage has been
set to an incorrect value.
The float voltage has been set to
an incorrect value.
The internal DC fuse is defective.
The absorption voltage has been
set to an incorrect value.
The float voltage has been set to
an incorrect value.
A defective battery.
The battery is too small.
The battery is too hot.
Alt. 1: Battery overtemperature
(> 50°C)
Alt 2: Battery temperature sensor
faulty
Solution
Ensure that the input voltage is
between 185 Vac and 265 Vac, and
that the frequency matches the
setting.
Reset the 16A thermal circuit breaker.
Set the charging current at between
0.1 and 0.2x battery capacity.
Check the battery terminals.
Adjust the absorption voltage to the
correct value.
Adjust the float voltage to the
correct value.
Inverter is damaged.
Adjust the absorption voltage to the
correct value.
Adjust the float voltage to the
correct value.
Replace the battery.
Reduce the charging current or use a
battery with a higher capacity.
Connect a temperature sensor.
- Allow battery to cool down
- Place battery in a cool environment
- Check for shorted cells
Unplug battery temperature sensor
from the EasyPlus.
Reset the EasyPlus by switching it off,
then wait for 4 seconds and switch it
on again
If the EasyPlus now charges normally,
the battery temperature sensor is
faulty and needs to be replaced