Herunterladen Inhalt Inhalt Diese Seite drucken

Electrical Connection - IFM Electronic efector 500 PN22 Bedienungsanleitung

Combi-drucksensor
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Electrical connection

The unit must be connected by a suitably qualified electrician.
The national and international regulations for the installation of
electrical equipment must be observed.
Voltage supply to EN50178, SELV, PELV.
The device shall be supplied from an isolating transformer having a
secondary Listed fuse rated as noted in the following table.
Control-circuit wire size
AWG
26
24
22
20
18
16
The device shall be connected only by using any R/C (CYJV2) cord,
having suitable ratings.
Disconnect power before connecting the unit as follows:
2 x p-switching
2: OUT2
4: OUT1
1 x p-switching / 1 x analogue
2: OUT2
4: OUT1
Core colours of ifm sockets: 1 = BN (brown), 2 = WH (white), 3 = BU (blue), 4 = BK (black).
22
Overcurrent protection
(mm
2
)
(0.13)
(0.20)
(0.32)
(0.52)
(0.82)
(1.3 )
1
BN
L +
2
WH
4
BK
3
BU
L
1
BN
L +
2
WH
4
BK
3
BU
L
Maximum protective device rating
Ampere
1
2
3
5
7
10
2 x n-switching
2: OUT2
4: OUT1
1 x n-switching / 1 x analogue
2: OUT2
4: OUT1
1
BN
L +
2
WH
4
BK
3
BU
L
1
BN
L +
2
WH
4
BK
3
BU
L

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis