5.3
Installation of Devices 8013/3.2 into the Panel
▶
Turn the union nut counter-clockwise as far as it will go.
▶
Push the actuator from the front through the panel opening, making sure the seal is seated
flat against the panel, and lock it in position.
▶
Align the contact block with the three tabs of the actuator and snap them together.
▶
Tighten the union nut against the panel.
Spring clamp terminals
Conductor connection to spring clamp terminals
▶
Section with spring clamp terminals (1)
(for connection cross-section, see the "Technical data" chapter).
▶
Open the spring clamp terminal with a screwdriver (blade – 0.6 x 3.5 mm) by inserting it
into the square cut-out and hold the terminal open (2).
▶
Insert the conductor into one of the rounded openings (3).
▶
Remove the screwdriver (4).
When installing devices with type 8013/3.1 connection chambers, see chapter 5.4.