CHAPTER 1 - INSTALLATION

1.1 Inspection

Inspect the inverter for any damage that may have occurred during shipping.
Check the nameplate on the inverter. Verify the inverter unit is the correct one for the application. The
numbering system for the inverter is as shown below.
SEVA-Inverter
Motor Capacity
055: 7.5 HP
110: 15 HP
185: 25 HP

1.2 Environmental Conditions

Verify ambient condition for the mounting location.
- Ambient temperature should not be below 14ºF (-10ºC) or exceed 104ºF (40ºC).
- Relative humidity should be less than 90% (non-condensing).
- Altitude should be below 3,300ft (1,000m).
Do not mount the inverter in direct sunlight and isolate it from excessive vibration.

1.3 Mounting

The inverter must be mounted vertically with sufficient horizontal and vertical space between adjacent
equipment (A= Over 6" (150mm), B= Over 2" (50mm)).
All manuals and user guides at all-guides.com
SEV
Series Name
075: 10 HP
150: 20 HP
220: 30 HP
B
L G I ndu st ri a l Sy s t em s
3
008
iS5
Input Voltage
4 : 380 ~ 460V (±10%) (50/60Hz)
UL Listed
(UL508C)
A