The Trouble Interface Module is an extension for the External Power Supply Unit Kit only. It is
the communication interface between the External Power Supply Unit Kit and the panel, and
transmits the following faults to the panel:
Additionally, with the programming software, the switching outputs can be programmed and
the settings for the line monitoring according to EN54-13 can be done.
The module is plugged next to the BCM-0000-B Battery Controller Module on the PRS 0002 A
Panel Rail Short and is power-supplied by the panel rail via the module bus (MOB). The
module's front side shows 4 LEDs, which indicate the operation and fault status.
Bosch Sicherheitssysteme GmbH
Mains fault
Battery fault
Battery internal resistance fault
BCM Battery Controller Module fault
Short 24 V outputs
Ground fault