Troubleshooting; Fuse Change - AEG PDU 10-2 Betriebsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

6

Troubleshooting

6.1

Fuse Change

Overloading the power distribution unit by exceeding the
maximum specified currents will result in the line-side
miniature fuse. This is shown optically by the indicator (LED)
positioned in the immediate vicinity of the fuse going out.
Only renew the fuse(s) using components of the same types.
In this case, it is permitted for the amperage to be reduced or
for the trigger characteristics used to be changed. This allows
selectivity criteria to be met, in particular for operation with
uninterruptible power supply units.
31
EN