Herunterladen Inhalt Inhalt Diese Seite drucken

Pneumatic Connections; Electrical Connections; Initialisation And Commissioning - Gemü 1434 mPos Original Einbau- Und Montageanleitung

Intelligenter stellungsregler
Vorschau ausblenden Andere Handbücher für 1434 mPos:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

4

Pneumatic connections

3
2
1
Connec-
Designation
tion
Air supply connection P (max.
1
10 bar)
Working connection for
2
process valve A1
Venting connection R with
3
integrated check valve
Housing ventilation with
E
integrated check valve
* only relevant for exhaust air duct and/or increase of
protection class
Max. air supply 8/10 bar!
5

Electrical connections

2
X1
3
5
1
4
X1
X3
Connection Pin Signal name
1
U
, 24 V DC supply voltage
v
I+ / U+, 4-20 mA/0-20 mA/0-10 V
2
(set value input)
X1
3
I- / U- GND
A-coded
I+ / U+, 4-20 mA/0-20 mA/0-10 V
M12 plug
4
(actual value output – optional)
U
, initialisation 24 V DC,
V
5
initialisation is started by an impulse
signal t ≥ 100 ms
For connection cables >30 m,
take precautionary measures
against surge voltage.
1434 µPos
All manuals and user guides at all-guides.com
In the version with external travel
sensor:
E
Connection Pin Signal name
Connection
size
M5
M12 socket
M5
M6 x 0.75*
M6 x 0.75*
Risk of cable break!
® Damage to the device.
2
X3
1
5
3
4
X1
6
X3
24 / 32
X3 is only required in
combination with an external
travel sensor system.
UP+, output potentiometer supply
1
voltage (+)
UP, input potentiometer wiper
2
X3
voltage
A-coded
UP-, output potentiometer supply
3
voltage (-)
4
n. c.
5
n. c.
Earth the positioner housing
(using mounting bracket).
Take ESD protective
measures when mounting the
potentiometer.
CAUTION
Turn electrical connections
max. 360°.
Initialisation and
commissioning
If the GEMÜ 1434 Pos is delivered
fully mounted to a valve ex works,
it is already preset at the factory
(at a control pressure of 5.5 – 6 bar
without operating pressure) and
is therefore ready for operation.
Reinitialisation (see chapter 7.2)
is recommended if the system is
operated under a diff erent control
pressure or if the mechanical end
positions have been changed (e.g.
seal replacement on the valve
or actuator replacement). The
initialisation is retained even in the
event of voltage cutoff .
2
3
5
1
4
max. 360°

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis