Features
Input "Weld Contactor Enable"
Output "Contactor open"
The Weld Contactor Output will be set with the receipt of a program start (internal
or external), if serial Input "Weld Contactor Enable" is high and ignition is set.
Output "Close Weld Contactor" will stay energized until serial Input "Weld
Contactor Enable" is set low, or a fault occurs, or E-Stop occurs, or a timeout
occurs.
A Timeout is defined as a period of time with no receipt of a "Start" signal. The
timeout is set for 60 seconds.
This input must be maintained high to allow Weld Contactor control logic to
function. The input may be used to open the Weld Contactor as necessary, i.e.
Tip Replacement. If this input is low during the receipt of a program start (with
ignition), an error message ("No weld contactor enable") is displayed.
This output is the inverted signal of input "Weld contactor feedback".
7.1.6
Tip dress programs
There shall be schedules reserved for tip dressing. There shall be Pre-dress
schedules which can be programmed to cut a new weld cap to the proper face
diameter and dress schedules which will remove the contamination on the tip and
reform cap back to proper face diameter.
The pre-dress schedules shall not be counted as one of the cap dresses allowed
before a "cap change" is requested.
Tab.11: Tip dress schedules
gun number
pre-dress schedule
1
60
2
63
Tip dress schedules:
Pre-Dress Schedules.
When the Pre-Dress Schedule is executed, the remaining Tip dress counter is
not decreased.
When the Pre-Dress Schedule is running, electrode counter is not increased.
The Pre-Dress Schedule will not reset "Electrodes are reset" output 1.12.
R911174196 | PSI 6xCx.766xx
dress schedule
61
62