HINWEIS
▶ UL marking
▶ Internal overload protection rated for 125 % of the rated FLA.
▶ Marquage UL
▶ Protection contre les surcharges conçue pour se déclencher à 125 % de l'intensité assignée
à pleine charge.
Absicherungsdaten
Branch Circuit Protection (BCP)
Short Circuit Current Ratings (SCCR) with Standard Fuses or Circuit Breaker
(Tested per UL61800-5-1, reference UL file E132659)
These devices are suitable for motor group installation when used with Standard Fuses or Cir-
cuit Breaker. For single motor installation, if the fuse value indicated is higher than 400 % of
the motor current (FLA), the fuse value has to be calculated. If the value of the fuse is below
two standard ratings, the nearest standard ratings less than the calculated value shall apply.
Inverter
Mains
Rated power
kW
hp
230 V, 3-ph
0.37
0.5
230 V, 3-ph
0.55
0.75
230 V, 3-ph
0.75
1
230 V, 3-ph
1.1
1.5
230 V, 3-ph
1.5
2
230 V, 3-ph
2.2
3
230 V, 3-ph
3
4
230 V, 3-ph
4
5
230 V, 3-ph
5.5
7.5
230 V, 3-ph
7.5
10
230 V, 3-ph
11
15
230 V, 3-ph
15
20
230 V, 3-ph
18.5
25
230 V, 3-ph
22
30
480 V, 3-ph
0.37
0.5
480 V, 3-ph
0.55
0.75
480 V, 3-ph
0.75
1
480 V, 3-ph
1.1
1.5
480 V, 3-ph
1.5
2
480 V, 3-ph
2.2
3
480 V, 3-ph
3
4
480 V, 3-ph
4
5
480 V, 3-ph
5.5
7.5
480 V, 3-ph
7.5
10
480 V, 3-ph
11
15
480 V, 3-ph
15
20
480 V, 3-ph
18.5
25
480 V, 3-ph
22
30
480 V, 3-ph
30
40
480 V, 3-ph
37
50
480 V, 3-ph
45
60
Standard Fuses (UL248)
Max.
Max. rated current
SCCR
kA
A
5
30
5
30
5
30
5
30
5
30
5
30
5
30
5
40
5
40
5
80
5
80
5
125
5
125
5
125
5
30
5
30
5
30
5
30
5
30
5
30
5
30
5
30
5
30
5
40
5
40
5
80
5
80
5
80
5
125
5
125
5
125
Elektrische Installation
Circuit Breaker (UL489)
Class
Max. SCCR
Max. rated current
kA
CF, J, T
5
CF, J, T
5
CF, J, T
5
CF, J, T
5
CF, J, T
5
CF, J, T
5
CF, J, T
5
CF, J, T
5
CF, J, T
5
CF, J, T
5
CF, J, T
5
CF, J, T
5
CF, J, T
5
CF, J, T
5
CC, CF, J, T
5
CC, CF, J, T
5
CC, CF, J, T
5
CC, CF, J, T
5
CC, CF, J, T
5
CC, CF, J, T
5
CC, CF, J, T
5
CC, CF, J, T
5
CC, CF, J, T
5
CC, CF, J, T
5
CC, CF, J, T
5
CC, CF, J, T
5
CC, CF, J, T
5
CC, CF, J, T
5
CC, CF, J, T
5
CC, CF, J, T
5
CC, CF, J, T
5
Anschluss nach UL
Absicherungsdaten
A
30
30
30
30
30
30
30
30
30
80
80
125
125
125
30
30
30
30
30
30
30
30
30
40
40
80
80
80
125
125
125
37