Technical data
EC-Examination of Conformity
Marking gas-Ex
Marking dust-Ex
Maximum value Ui
Maximum value Ii
Maximum value Pi
Effective internal capacity
Effective internal Inductivity
Temperature range in T6 (zone 1)
Temperature range in T5 (zone 1)
Temperature range in T4 (zone 1)
Temperature range in T3 (zone 1)
Temperature range dust Ex (zone 21)
Maximum surface temperature (zone 21)
Detection range water
Detection range oil
Detection range air
Stand-by time before availability
Switch-on delay
Switch-off delay
Material of sensor
Material of flange connection
Surface roughness
Certificate of material
Compressive strength [bar]
Compressive strength [psi]
Test voltage
Degree of protection [DIN 60529]
Connection
Accessories
Hans Turck GmbH & Co. KG | Witzlebenstraße 7 | 45472 Mülheim an der Ruhr | Germany | T +49 208 4952-0 | www.turck.com
TÜV 99 ATEX 1518
Group 1
` II 2 G Ex ib IIC T6 Gb
` II 2 D Ex ib IIIC T125°C Db
13.65 V
200 mA
690 mW
0.27 nF
1.3 µH
+10 °C ≤ Ta ≤ +40 °C
+10 °C ≤ Ta ≤ +55 °C
+10 °C ≤ Ta ≤ +90 °C
+10 °C ≤ Ta ≤ +120 °C
-20 °C ≤ Ta ≤ +85 °C
125 °C
1...100 cm/s
3...200 cm/s
-
typ. 8 (2...18) s
typ. 2 (1...13) s
typ. 2 (1...13) s
1.4539
-
-
-
60
870
500 VAC/50 Hz/60 s
IP67
2 m FEP-cable blue, 4 x 0,25 mm²
2 x gasket AFM 34 G 3/4
2