Herunterladen Inhalt Inhalt Diese Seite drucken

Startup And Operation; Startup; Operation; Operating Notes - Balluff BOS R090K U D1 S49-Serie Betriebsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

BOS R090K-_U-_ D1_-S49/S75/02
Photoelectric sensors – Diffuse sensors
6

Startup and operation

6.1

Startup

DANGER
Uncontrolled system movement
When starting up, if the sensor is part of a closed loop
system whose parameters have not yet been set, the
system may perform uncontrolled movements. This
could result in personal injury and equipment damage.
► Persons must keep away from the system's
hazardous zones.
► Startup must be performed only by trained technical
personnel.
► Observe the safety instructions of the equipment or
system manufacturer.
CAUTION
Red light / infrared light
If you look into the light beam emitted by the transmitter,
temporary blinding and irritation of the eyes is possible.
► Do not look into the light beam!
1. Check connections for tightness and correct polarity.
Replace damaged connections.
2. Turn on the system.
3. Check measured values and adjustable parameters
and realign and adjust the sensor, if necessary.
Check for the correct values, especially after
replacing the sensor or after repair by the
manufacturer.
www.balluff.com
6.2

Operation

CAUTION
Red light / infrared light
If you look into the light beam emitted by the transmitter,
temporary blinding and irritation of the eyes is possible.
► Do not look into the light beam!
No further protective measures are required for operation.
Adjust sensor
1. Position the sensor at the desired distance.
2. Turn the potentiometer counterclockwise (smallest
range) so that the green LED lights up and the yellow
LED is off (NO contact version) or on (NC contact
version).
3. Put the object to be detected in the beam path.
4. Turn the potentiometer slowly clockwise until the yellow
LED lights up (NO contact version) or goes out (NC
contact version). The object has been detected
(position a).
5. Remove the object: The yellow LED goes out (NO
contact version) or lights up (NC contact version).
6. Turn the potentiometer further clockwise until the
yellow LED lights up (NO contact version) or goes out
(NC contact version).
⇒ The background has been detected (position b).
⇒ If no background is detected, then position b
matches the max. setting.
7. Turn the potentiometer back to the center position
between positions a and b. The green LED must light
up.
6.3

Operating notes

Regularly check function of the sensor and all
associated components.
Take the sensor out of service whenever there is a
malfunction.
Check fasteners regularly and retighten if needed.
6.4

Cleaning

Keep the lens as free from soiling as possible (dust etc.)
and do not touch it (fingerprints).
Remove soiling
► Wipe off the lens with a lint-free cloth and alcohol
(ethanol, isopropanol).
6.5

Maintenance

The product is maintenance-free.
english
9

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis