Intended use

This electronic material moisture measuring device uses the capacitive meas-
uring principle and is suitable for non-destructive location and evaluation
of moisture distribution in walls, floors and ceilings. The device provides an
overview of the extent, distribution and severity of the moisture damage as
part of a building survey. It can be used in the material-independent INDEX
mode or the additional Building Material mode. Material characteristics are
available for cement screed, anhydrite screed, and concrete which can be
displayed as a CM % or mass %. This climate sensor allows the device to be
used as a hygrometer and provides other relevant parameters for analysing
the damage and moisture behaviour using the ambient temperature, humidity
and calculated dew point. The measured data can be transferred to a smart
phone via the digital connection interface.
The integrated material characteristics correspond to the specified
building materials and their designation. Building materials of the same
type but with different designation / composition / strength / density
can however affect the measurement result. Furthermore, building
materials will vary from manufacturer to manufacturer due to the way
!
they are produced. This is why, in the event of different product
compositions or unfamiliar construction materials, a one-off
comparative moisture measurement should be taken using methods
that can be calibrated (e.g. kiln-drying method). If different measured
values occur, they should either be viewed relatively or the index mode
for moisture/drying behaviour should be used.