Enteisungsdiagramm AMS10-8
Defrost timing chart (AMS10-8)
Compr. speed
EEVH
SH control
SC control
500 pulses
EEVC
ON
FAN
ON
4-way valve
1s
60s
40s after defrost
condition is fulfilled
Abkürzung
SC
SH
EEVH
EEVC
LP
24
Kapitel 4 | Funktionsbeschreibung
56rps
25 rps
500
OFF
OFF
SH≤ 5°C
2rps / 5s
Allowed when condition
meets
Fully closed
Suction SH+ target LP control
Defrost end
condition fulfilled
Erklärung
Unterkühlung
Überhitzung
Exp.ventil Heizung
Exp.ventil Kühlung
Niederdruck
Compr.
stopped
SH control
3s
ON
ON
80s
90s
NIBE AMS10