Herunterladen Inhalt Inhalt Diese Seite drucken

HYDAC ELECTRONIC EDS 3000 Bedienungsanleitung Seite 76

Elektronischer druckschalter
Vorschau ausblenden Andere Handbücher für EDS 3000:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

42
Events
Code
Type
36002 (0x8ca2) Error
36016 (0x8cb0) Error
36032 (0x8cc0) Warning
36350 (0x8dfe)
Error
36351 (0x8dff)
Error
Status: 2022-07-14
Name
User setup error
User setup is corrupt, device is running with factory settings
Primary value signal
Primary value update failed, device output is temporarily disabled
error
Primary value out of
Primary value is below or above its valid range and limited to the
range
corresponding lower or upper value
IO-Link V1.1 system test event 1: event appears by setting index 2
System Test Event 1
to value 240, event disappears by setting index 2 to value 241
IO-Link V1.1 system test event 2: event appears by setting index 2
System Test Event 2
to value 242, event disappears by setting index 2 to value 243
HYDAC ELECTRONIC GMBH
EDS 3000 IO-Link
Description
Part no.: 669897

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis