TA200DU
The technical specifications and charateristic curves for each current range can be found on our website
https://library.abb.com/r?cid=9AAC100113&q=TA200DU. For nominal currents between three and eight times the set-
point, the tolerance is +/- 20%
Example for the determination of a suitable overload relay:
The motor with enhanced safety has the following data:
400 V, 50 Hz/60Hz, 77 kW, I
According to the tripping curve below , the trip time is smaller than the time t
2
Std
1
20
10
5
4
3
2
min
1
50
40
30
20
s
10
7
5
4
3
2
1
0.1
0.05
0.01
0.005
1
1.2
1.5
2
= 132 A, I
/I
= 7.3, temperature class T3, time t
e
A
N
multiples of rated current
3 x Ie
5 x Ie
7.2 x Ie
three pole
Imin
three pole
Imax
two pole
3
6
7.2
4
multiples of rated current I
= 13 s
E
of the motor.
E
three pole
Imin 130 A
47,4 s
15,8 s
8,6 s
fuse
315 A
8
10
15
20
e
tripping time
two pole
Imax 175 A
31,8 s
20,0 s
11,6 s
7,6 s
4,3 s
6,4 s
gL.
30
40
80
100 x
60
8
I
e