5
Integration
Cycle Settings
Validation
Settings
www.balluff.com
This parameter can be used to influence the IO-Link communication speed. Calculated
using the multiplier and the time base, the IO-Link cycle time can be increased.
The time base is described in Table B3. The multiplier is entered in decimal form from
0...63.
Bit
7
6
5
4
3
Time
Multiplier
base
Possible values of MasterCycleTime and MiniCycleTime
Time base
Time Base
encoding
value
00
0,1 ms
01
0,4 ms
10
1,6 ms
11
Reserved
NOTE: The value 0,4 results from the minimum possible transmission time according to
A.3.7.
No validation: validation deactivated, every device will be accepted.
Compatibility: manufacturer ID and device ID are compared to the IO-Link device data.
Identity: manufacturer ID and device ID and serial number are compared to the
IO-Link device data. The IO-Link communication is only started if there is a match.
2
1
0
Bit 0 to 5: Multiplier
These bits contain a 6-bit multiplier for the
calculation of MasterCycleTime or MinCycle
Time. Permissible values for the multiplier
are
0 to 63.
Bit 6 to 7: Time Base
These bits specify the time base for the
calculation of MasterCycleTime or
MinCycleTime.
Calculation
Multiplier x Time Base
6,4 ms + Multiplier x Time Base
32,0 ms + Multiplier x Time Base
Reserved
Description
Cycle Time
0,4 ms to 6,3 ms
6,4 ms to 31,6 ms
32,0 ms to 132,8 ms
Reserved
17