Maintenance and repair

EN
LED "ERR", red
EN
EN
OFF
FLASHES
EN
EN
EN
EN
EN
EN
EN
ON
EN
EN
LED "M/S", blue
EN
EN
OFF
FLASHES
EN
EN
EN
ON
EN
EN
EN
EN
8 x LED, red
EN
OFF
EN
FLASHES
EN
EN
ON
11
Maintenance and repair

11.1 Maintenance

Consult the relevant national regulations to determine the type and extent of inspections.
Adapt inspection intervals to the operating conditions.
During maintenance of the device, check at least:
whether the clamping screws holding the electric lines are securely seated,
whether the device enclosure and / or protective enclosure have cracks or other visible signs of damage,
whether the permissible ambient temperatures are observed,
whether the device is used according to its designated use.
34
IS1+ Temperature Input Module
Zone 1
Module state
No error
External error
Incorrectly configured module Configuration is not correct
Outputs in safety position
Module error
Module state
Normal operation
External maintenance re-
quired
Maintenance required
Module state
Normal operation
Signal error
Compensation of resistance
sensor
Unauthorized work being performed on the device!
Risk of injuries and material damage!
Work performed on the device must only be carried out by appropriately authorized
and trained personnel.
Error source
Possible solution
--
--
Error in the field circuit; line
breakage or short circuit,
measuring range exceeded/
not reached
or a wrong module is con-
nected
Cyclic data transfer with the
automation system has been
interrupted
Module is defective
Error source
Possible solution
--
--
Ambient temperature is
outside the specification
Slot error or module is
damaged due to excessive
temperature or end of
service life reached
Error source
Possible solution
--
--
Line breakage or short
circuit, measuring range
exceeded/not reached
2-wire compensation
incorrect
WARNING
Check signal LEDs "red"
Eliminate the cause in the indicated
field circuit, check electric lines and
field devices
Change configuration in the
automation system or connect the
correct module
Check the cyclic data transfer of CPM
or CPU (LCD or LED "RUN")
Check bus connection
Activate the cyclic data transfer with
the automation system
Replace the module
Reduce ambient temperature, for ex-
ample by means of shading or cooling
Note: If the problem is not eliminated,
the module will be permanently
damaged
Replace the module as soon as
possible within the next 12 months,
otherwise, there is a risk of module
failure
Eliminate the cause in the indicated
field circuit, check electric lines and
field device
Repeat compensation
218149 / 948260310010
2014-04-17·BA00·III·en·00