Maintenance and repair
EN
LED "ERR", red
EN
EN
OFF
FLASHES
EN
EN
EN
EN
EN
EN
EN
ON
EN
EN
LED "M/S", blue
EN
EN
OFF
FLASHES
EN
EN
EN
ON
EN
EN
EN
EN
8 x LED, red
EN
OFF
EN
FLASHES
EN
EN
ON
11
Maintenance and repair
11.1 Maintenance
•
Consult the relevant national regulations to determine the type and extent of inspections.
•
Adapt inspection intervals to the operating conditions.
During maintenance of the device, check at least:
•
whether the clamping screws holding the electric lines are securely seated,
•
whether the device enclosure and / or protective enclosure have cracks or other visible signs of damage,
•
whether the permissible ambient temperatures are observed,
•
whether the device is used according to its designated use.
34
IS1+ Temperature Input Module
Zone 1
Module state
No error
External error
Incorrectly configured module Configuration is not correct
Outputs in safety position
Module error
Module state
Normal operation
External maintenance re-
quired
Maintenance required
Module state
Normal operation
Signal error
Compensation of resistance
sensor
Unauthorized work being performed on the device!
Risk of injuries and material damage!
•
Work performed on the device must only be carried out by appropriately authorized
and trained personnel.
Error source
Possible solution
--
--
Error in the field circuit; line
breakage or short circuit,
measuring range exceeded/
not reached
or a wrong module is con-
nected
Cyclic data transfer with the
automation system has been
interrupted
Module is defective
Error source
Possible solution
--
--
Ambient temperature is
outside the specification
Slot error or module is
damaged due to excessive
temperature or end of
service life reached
Error source
Possible solution
--
--
Line breakage or short
circuit, measuring range
exceeded/not reached
2-wire compensation
incorrect
WARNING
•
Check signal LEDs "red"
•
Eliminate the cause in the indicated
field circuit, check electric lines and
field devices
•
Change configuration in the
automation system or connect the
correct module
•
Check the cyclic data transfer of CPM
or CPU (LCD or LED "RUN")
•
Check bus connection
•
Activate the cyclic data transfer with
the automation system
•
Replace the module
•
Reduce ambient temperature, for ex-
ample by means of shading or cooling
Note: If the problem is not eliminated,
the module will be permanently
damaged
•
Replace the module as soon as
possible within the next 12 months,
otherwise, there is a risk of module
failure
•
Eliminate the cause in the indicated
field circuit, check electric lines and
field device
•
Repeat compensation
218149 / 948260310010