3 INSTALLATION
3.2.10 Wiring of a wall-mounted version, 115/230 VAC, without relay
Install the transmitter as described in § 3.1.3. Unscrew the 4 screws of the cover and uns-
crew the cable glands. Pass the cables through the cable glands by preferably respecting
the allocation indicated in fig. 3.14. Connect according to pin assignment below.
Only manipulate the switch when the device is not powered.
(*) wired ex-works
1 2 3 4
Fit here the
cables using the
NC
Without
With
Iout
supplied cable
clips
(see § 3.2.3)
1 2 3 4 PE
PT SENSOR
Temperature
sensor connection:
1 : red wire
2 : blue wire
redox sensor con-
3 : white wire
4 : green/yellow wire
nection
PE : shielding of the cable
1
2
Pt1000
3
4
PE
Equipotential of the medium
Fig. 3.17 Wiring of the transmitter, wall-mounted version, 115/230 VAC, without relay
REDOX TRANSMITTER 8206
Connection of the
shielding of the power
supply cable *
CURRENT
SOURCE
SINK
PE
L+
L-
PE
L+
L-
PE
Supply
12..30Vdc
PH SENSOR
3A/230VAC
Strap to be removed
if the transmitter is
connected to a PLC
E-21-
All the cables must
be fitted here
230/115 VAC
power supply
selection switch
Fuse
5 6 7 8 9 10
+ -
4-20 mA
PLC
L N
Connect the
115/230 VAC
power supply